13
User Manual
SCANEX PLUS
Bottom Clipping to 3000.0
(Default : 100.0)
(Default : Disable)
Enable
Disable
TOP CLIPPING ENABLE
(Applicable only for DC Linear Inputs)
Refer Appendix-B.
TOP CLIPPING
(Applicable only for DC Linear Inputs)
Refer Appendix-B.
Parameter Description
Settings
(Default Value)
Table 5.2
Resolution
Option
What it means
Range (Min. to Max. )
Type J Thermocouple
Type K Thermocouple
Type T Thermocouple
0.0 to +960.0°C / +32.0 to +1760.0°F
-200.0 to +1376.0°C / -328.0 to +2508.0°F
-200.0 to +387.0°C / -328.0 to +728.0°F
Type R Thermocouple
Type S Thermocouple
Type B Thermocouple
Type N Thermocouple
0.0 to +1771.0°C / +32.0 to +3219.0°F
1 °C/°F
or
0.1 °C/°F
3-wire, RTD Pt100
-199 to +600°C / -328 to +1112°F
-199.9 to +600.0°C / -328.0 to +1112.0°F
or
1 °C/°F
or
0.1 °C/°F
0.0 to +1314.0°C / +32.0 to +2397.0°F
0.0 to +1826.0°C / +32.0 to +3218.0°F
0.0 to +1768.0°C / +32.0 to +3214.0°F
R
eserved for customer specific Thermocouple type not listed
above. The type shall be specified in accordance with the
ordered (optional on request) Thermocouple type.
-1999.9 to 3000.0
(Default : 0.0)
OFFSET
In many application, the measured
PV
at the input requires a
constant value to be added or subtracted to obtain a final process
value for removing sensor zero error or to compensate known
thermal gradient. This parameter is used to remove such errors.
Actual (Displayed) PV = Measured PV + Offset for PV.