24
User Manual
neuro 202
Settings
(Default Value)
Parameter Description
OP2 EVENT TIME
(Available if Output-2 function is End of Profile & Event Status is
set to ‘ON’)
Set the time (in selected units) for which the Output-2 status after
the End of Profile is to be maintained. (For indefinite time interval,
set the value to 0).
(Default : 0)
0 to 9999
OP2 EVENT TIME UNITS
(Available if Output-2 function is End of Profile & Event Status is
set to ‘ON’)
Select time units for the parameter ‘Output-2 Event Time’.
(Applicable for Output-3 hardware module, if fitted)
Select the function / feature that will utilize Output-3 module as
output.
OUTPUT-3 FUNCTION SELECTION
(Available if Output-3 function is Alarm-2 Output)
Select ‘Normal’ if Alarm-2 is to activate an Audio / Visual alarm.
Select ‘Reverse’ if Alarm-2 is to Trip the system.
ALARM-2 LOGIC
Reverse
Normal
(Default : Normal)
(Available if Output-3 function is End-of-Profile)
Definition same as Output-2 Event Status .
OUTPUT-3 EVENT STATUS
(Default : ON)
OFF
ON
(Default : 0)
0 to 9999
(Available if Output-3 function is End of Profile & Event Status is
set to ‘ON’)
Definition same as Output-2 Event Time.
OUTPUT-3 EVENT TIME
OUTPUT-3 EVENT TIME UNITS
(Available if Output-3 function is End of Profile & Event Status is
set to ‘ON’)
Definition same as Output-2 Event Time Units.
None
Alarm-2
Recorder
End Of Profile
(Default : Alarm)
(Default : Seconds)
Seconds
Minutes
Hours
(Default : Seconds)
Seconds
Minutes
Hours