27
HumiTherm Ultra
User Manual
Display Range Low
(Available for DC Linear Volts & mA Inputs only)
Range : -199.9 to Range High
Default : 0.0
This parameter is the rocess alue that correspond to the Signal Low value from
P
V
s
the transmitter. Refer
Appendix-A : DC
Linear Signal Interface
for details.
Display Range High
(Available for DC Linear Volts & mA Inputs only)
Range : Range Low to 999.9
Default : 100.0
Th
Process alue that correspond to the Signal High value from the transmitter.
is parameter is the
V
s
Refer
Appendix-A : DC
Linear Signal Interface
for details.
Zero offset
Range : -50.0 to 50.0 °C
Default : 0.0 °C
This value is algebraically added to the measured Temperature Value to derive the final Value that is displayed and compared
for alarm / control. Use this value to nullify any known constant error.
Final Value = Measured Value + Offset
Factory
Temperature
Alarm Settings
5.0
5.0
2.0
Inhibit
Options Enable, Disable
:
Default : Enable
If this parameter is set to ‘
’, the Alarm activation is suppressed until the Temperature value is within Alarm limits from the
Enable
time the controller is switched ON. This allows suppressing the Alarm during the start-up Alarm conditions.
If this parameter is set to ‘Disable’, the Alarm is not suppressed during the start-up Alarm conditions.