15
HumiTherm Plus for PC
User Manual
Sets derivative time constant in Seconds for Cool Pre-dominant
zone. Setting the value to 0, cuts-off derivative action.
CZ DERIVATIVE TIME >>
(Default :
)
16 Sec
0 to 600 Sec
Sets the total ‘On + Off’ time in seconds for time proportional
power output through Relay / SSR.
CYCLE TIME >>
(Default :
.0 Sec)
10
0.5 to 100.0 Sec
Parameter Description
Settings
(Default Value)
Sets proportional gain for Cool Pre-dominant zone.
CZ PROP BAND >>
(Default :
)
50.0
0.1 to 999.9
Sets integral time constant in Seconds for Cool Pre-dominant
zone. Setting the value to 0, cuts-off integral action.
CZ INTEGRAL TIME >>
(Default :
)
100 Sec
0 to 3600 Sec
Control Zones : Dual
Sets derivative time constant in Seconds for Heat Pre-dominant
zone. Setting the value to 0, cuts-off derivative action.
HZ DERIVATIVE TIME >>
(Default :
)
16 Sec
0 to 600 Sec
Sets proportional gain for Heat Pre-dominant zone.
HZ PROP BAND >>
(Default :
)
50.0
0.1 to 999.9
Sets integral time constant in Seconds for Heat Pre-dominant
zone. Setting the value to 0, cuts-off integral action.
HZ INTEGRAL TIME >>
(Default :
)
100 Sec
0 to 3600 Sec
Control Zones : Single
Sets derivative time constant in seconds. Setting the value to 0,
cuts-off derivative action.
DERIVATIVE TIME >>
(Default :
)
16 Sec
0 to 600 Sec
Sets the total ‘On + Off’ time in seconds for time proportional
power output through Relay / SSR.
CYCLE TIME >>
(Default :
.0 Sec)
10
0.5 to 100.0 Sec
Sets proportional gain (% output power per unit error).
PROPORTIONAL BAND >>
(Default :
)
50.0
0.1 to 999.9
Sets integral time constant in Seconds. Setting the value to 0,
cuts-off integral action.
INTEGRAL TIME >>
(Default :
)
100 Sec
0 to 3600 Sec