User Manual
HumiTherm-i Pro
14
PAGE-14 : DE-HUMIDIFIER CONTROL PARAMETERS
Table 8.1
Parameter Description
Settings
(Default Value)
Section 8
(Default : Disable)
Disable
Enable
(Default : 0)
0.0 to 100.0
(Default : 2.0)
0.1 to 99.9
DE-HUMIDIFIER CONTROL
Set this parameter to Enable if Humidifier Control is desired. If
enabled, the measured %RH value is compared with the set value
and a relay output is switched.
DE-HUMIDIFIER SETPOINT
If the measured %RH value becomes equal or exceed this
setpoint value, the de-humidifier control output relay is switched-
On.
De-humidifier ON condition
:
%RH >= De-humidifier Setpoint
DE-HUMIDIFIER HYSTERESIS
If the measured %RH value becomes equal or falls below the
setpoint minus hysteresis, the de-humidifier control output relay is
switched- Off.
De-humidifier OFF condition
:
%RH <= (De-humidifier Setpoint - De-humidifier Hysteresis)