Chapter 5 Function parameter
50
Ch
ap
ter 5
400.
E2.16 Proportional gain KP2
0.0 to 200.0
20.0
☆
401.
E2.17 Integration time Ti2
0.01s to 10.00s
2.00s
☆
402.
E2.18 Differential time Td2
0.00 to 10.000
0.000s
☆
403.
E2.19
PID parameter switching
conditions
0: no switching
1: switching via terminals
2: automatically switching
according to deviation.
0
☆
404.
E2.20
PID parameter switching
deviation 1
0.0% to E2.21
20.0%
☆
405.
E2.21
PID parameter switching
deviation 2
E2.20 to 100.0%
80.0%
☆
406.
E2.22 PID integral properties
Units digit: integral separation
0: Invalid; 1: Valid
Tens digit: whether stop integration
when output reaches limit
0: continue; 1: stop
00
☆
407.
E2.23 PID initial value
0.0% to 100.0%
0.0%
☆
408.
E2.24 PID initial value hold time
0.00s to 360.00s
0.00s
☆
409.
E2.25
Maximum deviation of twice
outputs(forward)
0.00% to 100.00%
1.00%
☆
410.
E2.26
Maximum deviation of twice
outputs(backward)
0.00% to 100.00%
1.00%
☆
411.
E2.27
Computing status after PID
stop
0: stop without computing
1: stop with computing
1
☆
412.
E2.28 reserved
413.
E2.29
PID automatic decrease
frequency selection
0
:
invalid
;
1
:
valid
0
☆
414.
E2.30 PID stop frequency
0.00Hz~maximum
frequency(F0.19)
25
☆
415.
E2.31 PID checking time
0s~3600s
10
☆
416.
E2.32 PID checking times
10~500
20
☆
5-1-18.
E3 Group – Virtual DI
、
Virtual DO
No.
Code
Parameter name
Setting range
Factory
setting
Chan
ge
417.
E3.00
Virtual VDI1 terminal function
selection
0 to 50
0
★
418.
E3.01
Virtual VDI2 terminal function
selection
0 to 50
0
★