Chapter 5 Function parameter
42
Ch
ap
ter 5
selection
protection selection
0: Invalid 1: Enable
Tens digit:contactor actuation
protection
0: Invalid 1: Enable
265.
F8.08
Output phase loss
protection selection
0: Invalid 1: Enable
1
☆
266.
F8.09 Short to ground protection 0:Invalid 1: Valid
1
☆
267.
F8.10
Number of automatic fault
reset
0 to 32767
0
☆
268.
F8.11
Fault DO action selection
during automatic fault
reset
0: OFF
1: ON
0
☆
269.
F8.12
Automatic fault reset
interval
0.1s to 100.0s
1.0s
☆
270.
F8.13
Over-speed detection
value
0.0 to 50.0% (maximum frequency)
20.0%
☆
271.
F8.14 Over-speed detection time 0.0 to 60.0s
1.0s
☆
272.
F8.15
Detection value for too
large speed deviation
0.0 to 50.0% (maximum frequency)
20.0%
☆
273.
F8.16
Detection time for too
large speed deviation
0.0 to 60.0s
5.0s
☆
274.
F8.17
Fault protection action
selection 1
Units digit: Motor overload (Err.11)
0: Free stop
1: Stop at the selected mode
2: Continue to run
Tens digit: input phase loss (Err.12)
(same as units digit)
Hundred digit: output phase loss
(Err.13) (same as units digit)
Thousand digit: external fault
(Err.15) (same as units digit)
Ten thousands digit: Communication
abnormal( Err.16)(same as units
digit)
00000
☆
275.
F8.18
Fault protection action
selection 2
Units digit: Encoder fault(Err.20)
0: Free stop
1:Switch to V/F and then stop at the
selected mode
2:Switch to V/F and continue to run
Tens digit: function code read and
write abnormal (Err.21)
0: Free stop
1: Stop at the selected mode
Hundreds digit: Reserved
Thousands digit: Motor overheating
00000
☆