Chapter 4 Function parameter description

12

F0.04 Voltage modulation factor

0%

200%

100%

This parameter can be used to adjust the d0.00 bus voltage detection value.

That is d0.00

DC BUS input voltage =d0.00*F0.04.

F0.05 Relay output function selection

0

4

0

Relay function instructions below:

Setting

value

Function

Description

0

No output

The relay outputs no action.

1

In Braking

In braking state, the relay outputs ON signal.

2

Braking feedback fault

(IGBT short circuit)

In braking process, it feedback IGBT short-circuit fault, the

relay output ON signal.

3

Over-temperature alarm

When the module temperature exceeds 85

, the over-

temperature alarm signal is generated, the relay outputs ON

signal.

4

Fault output

When brake feedback fault or over-temperature fault

occurs, the relay output ON signal.

F0.06 Master and slave selection

Slave

0

1

aster

1

This parameter is used for the parallel function, setting the braking unit as master or slave. If

you do not use the parallel function, the system single-set default unit host.

F0.07 Temperature hysteresis value

0

50

3

This parameter is used to set the hysteresis value of the temperature. The default temperature

alarm value for the brake unit is 85

. If the temperature hysteresis value is set to 3

, when

there is not over temperature fault, if only the temperature exceeds 85

, it alrms. If over

temperature fault occurs, the alarm is canceled only when the temperature drops below 82

.

F0.08 Total power-on time

0~50000h

-

Display the total power-on time of braking unit since it is out of factory.

F0.09 Total running time

0~50000h

-

F0.10 Parameter

initialization

No operation

0

0

The parameters restored to factory value

1

Clear record information

2

1: Restore to the factory setting (F0.10 = 1), most of the brake unit parameters are restored to

factory setting, except default braking voltage level (F0.02), fault record information, total power-

on time, total running time.

2: Clear the record information (F0.10 = 2) Clear the fault record information, total power-on

time, total running time of the braking unit.

4-1-3. Fault query

Code

Parameter name

Setting range

Factory

setting

Cha

nge

y1.00 Type of the first fault

0

2

-

y1.01 Type of the second fault

0

2

-

y1.02 Type of the third(at last) fault

0

2

-

Record the type of the last three faults of PB200, 0 for no fault. Please refer to the related

Summary of Contents for PB200 Series

Page 1: ......

Page 2: ...when using this product please contact your local dealer authorized by this company or directly contact this company our professionals are happy to serve you The end users should hold this manual and...

Page 3: ...setting 9 3 5 1 Description of Function code viewing and modifying method 9 Figure 3 2 Operational flow chart 9 3 5 2 Viewing method of state parameters 10 Chapter 4 Function parameter description 11...

Page 4: ......

Page 5: ...dealer or directly contact this company 1 1 Inspection after unpacking Check if that packing container contains this unit one manual and one warranty card Check the nameplate on the side of the freque...

Page 6: ...than DC 36V Power off more than ten minutes Otherwise the residual charge from capacitor would cause personal injury Attention Do not use any brake unit and brake resistor lack of or with damaged spar...

Page 7: ...0 100 PB200 180 3 670 180 PB200 250 3 670 250 PB200 040 4 760 40 PB200 050 4 760 50 PB200 075 4 760 75 PB200 100 4 760 100 PB200 180 4 760 180 PB200 250 4 760 250 2 2 Main circuit terminal screw speci...

Page 8: ...ve 50 C 2 Prevent electromagnetic interference and keep away from interference sources 3 Prevent the intrusion of dust cotton wool and fine metal powder 4 Prevent the intrusion of oil salt and corrosi...

Page 9: ...s and installation 5 Fan Case base Case cover Control keyboard Indicator light Air inlet board Figure 2 2 180 250A the braking unit sketch 80 110 202 80 7 216 186 216 140 2 R3 5 Figure 2 3 40 100A Bra...

Page 10: ...al specifications and installation 6 Figure 2 4 180 250A Braking unit installation dimension 2 5 Wiring diagram RB1 RB2 TA TB TC Frequency inverter Brake unit Brake resistor Figure 2 5 Single brake un...

Page 11: ...f main circuit will cause damage of brake unit and frequency inverter 6 Please do not touch the brake unit when it is working to avoid scald 2 5 1 Brake unit main circuit terminal and making circuit t...

Page 12: ...ult indicator light 3 3 Operation panel button instruction Mark Name Function Parameter setting ESC key Enter the first level menu parameters changes state Exit function data modify Exit from submenu...

Page 13: ...r setting 3 5 1 Description of Function code viewing and modifying method PB200 operation panel adopts three level menu structure to set parameters and other operations The three level menus are funct...

Page 14: ...h Press PRG Press ENTER Press ENTER Press ENTER Press PRG Press Press Flash Flash Flash Flash Press ENTER Example 2 Restore factory parameters Press Flash Press PRG Press ENTER Press ENTER Press ENTER...

Page 15: ...100V 20V This parameter is used to set the hysteresis voltage during braking Generally when setting braking start voltage and braking stop voltage there must be a hysteresis loop Such as settings F0...

Page 16: ...3 This parameter is used to set the hysteresis value of the temperature The default temperature alarm value for the brake unit is 85 If the temperature hysteresis value is set to 3 when there is not o...

Page 17: ...last fault y1 08 Bus voltage of the second fault Bus voltage of the previous fault y1 09 Temperature of the second fault Temperature of the previous fault y1 10 Braking rate of the second fault Brakin...

Page 18: ...ke resistor resistance selection When it is braking the regenerative energy of the motor is almost consumed on the brake resistor according to the formula U U R Pb In the formula U braking voltage in...

Page 19: ...7kW 2 132 PB200 180 2 2 2 8kW 2 160 PB200 100 2 2 2 9kW 2 2 This table is the selection reference of 380V inverter according to the brake unit DC operating point 670V braking frequency ED 10 and brak...

Page 20: ...pcs 18 5 PB200 040 4 1 19 2kW 1 22 PB200 040 4 1 19 3kW 1 30 PB200 040 4 1 19 3kW 1 37 PB200 040 4 1 19 4kW 1 45 PB200 050 4 1 16 5kW 1 55 PB200 075 4 1 11 6kW 1 75 PB200 075 4 1 11 8kW 1 93 PB200 100...

Page 21: ...cess please contact POWTRAN technical service personnel Table 6 1 List of braking unit fault diagnosis and protection functions No Error code Error type Possible causes Solutions 1 E SHo Braking feedb...

Page 22: ...check tighten and clean No abnormal Electrolytic capacitance Whether appearance is abnormal or not Visually check No abnormal Wires and conducting bar Whether they are loose or not Visually check No a...

Page 23: ...or metal dust and the ambient temperature complies with the range stipulated by standard specification 2 Voltage withstand test can not be arbitrarily implemented it will reduce the life of inverter L...

Page 24: ...use the user use environment device caused by aging lead to product failure 2 6 Due to the fault cause of earthquake fire lightning wind or water disaster abnormal voltage irresistible natural disaste...

Page 25: ...Modified record Serial No Modified date Modified content record Modified version 1 2 3...

Page 26: ...dback For your convenience please visit our website http www powtran com and then click Technologies and Services and Download columns to submit your feedback information 1 Download the update product...

Page 27: ...PB200 Brake unit English Manual V1 1...

Reviews: