Chapter 4 Function parameter description
12
F0.04 Voltage modulation factor
0%
~
200%
100%
☆
This parameter can be used to adjust the d0.00 bus voltage detection value.
That is d0.00
=
DC BUS input voltage =d0.00*F0.04.
F0.05 Relay output function selection
0
~
4
0
☆
Relay function instructions below:
Setting
value
Function
Description
0
No output
The relay outputs no action.
1
In Braking
In braking state, the relay outputs ON signal.
2
Braking feedback fault
(IGBT short circuit)
In braking process, it feedback IGBT short-circuit fault, the
relay output ON signal.
3
Over-temperature alarm
When the module temperature exceeds 85
℃
, the over-
temperature alarm signal is generated, the relay outputs ON
signal.
4
Fault output
When brake feedback fault or over-temperature fault
occurs, the relay output ON signal.
F0.06 Master and slave selection
Slave
0
1
★
aster
1
This parameter is used for the parallel function, setting the braking unit as master or slave. If
you do not use the parallel function, the system single-set default unit host.
F0.07 Temperature hysteresis value
0
~
50
3
☆
This parameter is used to set the hysteresis value of the temperature. The default temperature
alarm value for the brake unit is 85
℃
. If the temperature hysteresis value is set to 3
℃
, when
there is not over temperature fault, if only the temperature exceeds 85
℃
, it alrms. If over
temperature fault occurs, the alarm is canceled only when the temperature drops below 82
℃
.
F0.08 Total power-on time
0~50000h
-
●
Display the total power-on time of braking unit since it is out of factory.
F0.09 Total running time
0~50000h
-
●
F0.10 Parameter
initialization
No operation
0
0
★
The parameters restored to factory value
1
Clear record information
2
1: Restore to the factory setting (F0.10 = 1), most of the brake unit parameters are restored to
factory setting, except default braking voltage level (F0.02), fault record information, total power-
on time, total running time.
2: Clear the record information (F0.10 = 2) Clear the fault record information, total power-on
time, total running time of the braking unit.
4-1-3. Fault query
Code
Parameter name
Setting range
Factory
setting
Cha
nge
y1.00 Type of the first fault
0
~
2
-
●
y1.01 Type of the second fault
0
~
2
-
●
y1.02 Type of the third(at last) fault
0
~
2
-
●
Record the type of the last three faults of PB200, 0 for no fault. Please refer to the related