ALARM SETTING

PROCEDURE FOR SETTING ALARM ON TC310VP

For alarm setting purposes, the controller may be in either the control or the open loop mode, provided that
the input signal from the sensor to the controller remains steady at any convenient level during the short
period of time that it takes to set the alarm level.

1. STEPS IN SETTING UP A HIGH ALARM LEVEL

1.1 Ensure that the sensor input to the controller is at a steady temperature T1.

1.2 Turn the alarm setting control P12 fully clockwise.

1.3 Decide how many degrees above the set temperature the alarm must operate. Let this be t degrees.

1.4 By means of the thumbwheel, adjust the set temperature of the controller to be t degrees lower than the
sensor input temperature T1.

1.5 Adjust the alarm setting control P12 anti-clockwise until the alarm relay LED just comes on. The high
alarm will now operate at t degrees above any chosen set point temperature.

2. STEPS IN SETTING A LOW ALARM LEVEL

2.1 Ensure that the sensor input to the controller is at a steadytemperature T1.

2.2 Turn the alarm setting control P12 fully clockwise.

2.3 Decide how many degrees below the set temperature the alarm must operate. Let this be t degrees.

2.4 By means of the thumbwheel, adjust the set temperature of the controller to be t degrees higher than the
sensor input temperature T1.

2.5 Adjust the alarm settin congtrol P12 anti-clockwise until the alarm relay LED just comes on.The low alarm
will now operatre at t degrees below any chosen set point temperature.

3. STEPS IN SETTING UP A BAND ALARM

The band alarm operates when the actual temperature is t degrees higher than the set temperature or t
degrees lower than the set temperature. Therefore the band alarm may be set by setting up the high end in
the same manner as section one above or by setting the low end in the same manner as section two above.

14 March 1995

- 6 -

310VPIM

Issue 2.0

Summary of Contents for Tactical 310

Page 1: ...OLLER WITH VALVE POSITIONER OUTPUT INSTRUCTION MANUAL CONTENTS DESCRIPTION 2 INSTALLATION 2 CONNECTIONS 3 CONTROL ADJUSTMENTS 4 TUNING 5 ALARM SETTING 6 TECHNICAL SPECIFICATION 7 ORDERING INFORMATION...

Page 2: ...etpoint changeover switch on the front panel Setpoint adjustment is made by turning the setpoint thumbwheel which is concealed behind the door on the front panel Wiring connections are made at the bac...

Page 3: ...TC310VP Instruction Manual Powtier Controls Limited CONNECTIONS Typical TC310VP wiring Schematic Terminal connection diagram 14 March 1995 3 310VPIM Issue 2 0...

Page 4: ...nual Reset optional can be used to remove the steady state error inherent in PD control P10 Not used P11 Not used P12 High Low Band Alarm optional only one type on any instrument can be used to give a...

Page 5: ...to table 2 8 Progressively reset P13 P14 as far clockwise as possible without the introduction of system hunting Table 1 Switch settings for integral and derivative time constant SID ti td SID ti td 1...

Page 6: ...just comes on The high alarm will now operate at t degrees above any chosen set point temperature 2 STEPS IN SETTING A LOW ALARM LEVEL 2 1 Ensure that the sensor input to the controller is at a steady...

Page 7: ...span Derivative time td 0 5 to 5 minutes Manual reset PD control only 0 to 50 output power at span ON OFF control option Hysteretic 0 5 of span ALARMS OUTPUTS option Relay Normally energised and de en...

Page 8: ...r 49 OPTIONS No option 01 Low deviation alarm 21 High deviation alarm 22 Band deviation alarm 23 Two term PD Control 31 On off control 32 Downscale Thermocouple break protection 61 Retransmission sign...

Reviews: