TUNING

PID CONTROL TUNING PROCEDURE

1. Set P13 and P14 fully counter clockwise.

2. Set proportional band to minimum (P1 fully anticlockwise).

3. Set all SID switches to ’ON’ (11111111).

4. Adjust the setpoint to 10% below working temperature.

N.B. If it is undesirable for the system to overshoot the working temperature, perform the test at a further
reduced temperature.

5. Observe:-

a. Time (to) taken for the measured temperature to rise from the setpoint to a maximum.

b. Overshoot temperature (To) = maximum temperature - setpoint temperature.

6. Set the SID switches (see Table 1) to give ti = 4 x to. This will automatically set td = ti/9.

7. From the overshoot temperature, To, calculate the proportional band index PBI as follows:-

PBI = (To / TR) x 100

TR = 200 for -50 to 200 range

TR = 500 for -50 to 500 range

TR = 1000 for 0 to 999 range

and set the proportional band according to table 2.

8. Progressively reset P13 & P14 as far clockwise as possible without the introduction of system hunting.

Table 1. Switch settings for integral and derivative time constant.

SID

ti

td

SID

ti

td

12345678

(minute)

(minute)

12345678

(minute)

(minute)

00000000

50

5.5

10001000

23

2.6

00010001

46

5.2

10011001

20

2.2

00100010

43

4.8

10101010

17

1.9

00110011

40

4.4

10111011

13

1.5

01000100

36.5

4.1

11001100

10

1.1

01010101

33

3.7

11011101

7

0.8

01100110

30

3.3

11101110

3

0.4

01110111

27

3.0

11111111

ON/OFF

CONTROL

(For SID switch, 0 - off, 1 – on)

Table 2. Proportional band index.

P1 MARKING

PBI

P1 MARKING

PBI

P1 MARKING

PBI

0

1

4

8.9 – 11.5

8

19.6 – 22.3

1

1 – 3.5

5

11.5 – 14.2

9

22.3 – 25.0

2

3.5 – 6.2

6

14.2 – 17.0

10

25

3

6.2 – 8.9

7

17.0 – 19.6

PD CONTROL (OPTIONAL) TUNING PROCEDURE

1. Turn the manual reset to minimum (P3 fully anticlockwise).

2. Proceed as for PID control tuning procedure, use table 1 to set SID to give td = 0.5 x to.

3. Turn P3 anticlockwise to eliminate any steady state error.

ON-OFF CONTROL (OPTIONAL) TUNING PROCEDURE

No adjustment is required for ON-OFF control.

14 March 1995

- 5 -

310VPIM

Issue 2.0

Summary of Contents for Tactical 310

Page 1: ...OLLER WITH VALVE POSITIONER OUTPUT INSTRUCTION MANUAL CONTENTS DESCRIPTION 2 INSTALLATION 2 CONNECTIONS 3 CONTROL ADJUSTMENTS 4 TUNING 5 ALARM SETTING 6 TECHNICAL SPECIFICATION 7 ORDERING INFORMATION...

Page 2: ...etpoint changeover switch on the front panel Setpoint adjustment is made by turning the setpoint thumbwheel which is concealed behind the door on the front panel Wiring connections are made at the bac...

Page 3: ...TC310VP Instruction Manual Powtier Controls Limited CONNECTIONS Typical TC310VP wiring Schematic Terminal connection diagram 14 March 1995 3 310VPIM Issue 2 0...

Page 4: ...nual Reset optional can be used to remove the steady state error inherent in PD control P10 Not used P11 Not used P12 High Low Band Alarm optional only one type on any instrument can be used to give a...

Page 5: ...to table 2 8 Progressively reset P13 P14 as far clockwise as possible without the introduction of system hunting Table 1 Switch settings for integral and derivative time constant SID ti td SID ti td 1...

Page 6: ...just comes on The high alarm will now operate at t degrees above any chosen set point temperature 2 STEPS IN SETTING A LOW ALARM LEVEL 2 1 Ensure that the sensor input to the controller is at a steady...

Page 7: ...span Derivative time td 0 5 to 5 minutes Manual reset PD control only 0 to 50 output power at span ON OFF control option Hysteretic 0 5 of span ALARMS OUTPUTS option Relay Normally energised and de en...

Page 8: ...r 49 OPTIONS No option 01 Low deviation alarm 21 High deviation alarm 22 Band deviation alarm 23 Two term PD Control 31 On off control 32 Downscale Thermocouple break protection 61 Retransmission sign...

Reviews: