WARNING:  

OF  HIGH  NEUTRAL  TO  GROUND  VOLTAGE

On certain models, a RED warning light is provided.  Should this light
glow RED at  any time, consult a qualified electrical contractor to check
the integrity of  the  building wiring.  This RED light does not  indicate
suppressor failure, however a RED glowing light is indicative of poten-
tially hazardous site wiring.

3

S

TATUS

  I

NDICATORS

The 

Powerware TVSS ZoneMaster

® 

PLUS

 units have comprehensive, continuous visual

status monitoring present on each module.

R

EMOTE

  I

NDICATORS

A remote indication of the reduced protection state is available as a
normally open or normally closed dry contact.

Status

Indicated

Indication

Windows

LED

Indicator

Full

Protection

Present

Both

Windows

Show

Green

Green

LED

Lit

Reduced

(Standby)

Protection

One

Window

Shows

Black

Green

LED

Lit

No

Protection

Both

Windows

Show

Black

Green

LED

Out

No

Power To
Protector

Both

Windows

Show

Green

Green

LED

Out

NOTE: Line-ground modules DO NOT have "Power/

Protection" LED

Summary of Contents for TVSS ZoneMaster PLUS

Page 1: ...ZONEMASTER PLUS AC Panel Transient Voltage Surge Suppressors Installation Instructions User Manual Powerware TVSS...

Page 2: ...ANEL PROTECTORS Particularly important is the length of the connecting leads see pages 4 5 INTRODUCTION This document explains how to install the Powerware TVSS ZoneMaster PLUS AC Panel Surge Protecti...

Page 3: ...TVSS ZoneMaster PLUS units have comprehensive continuous visual status monitoring present on each module REMOTE INDICATORS A remote indication of the reduced protection state is available as a normal...

Page 4: ...COMMENDED WIRE GAUGE Minimum of 8 AWG Maximum of 4 AWG for ease of dressing LENGTH OF CONNECTING LEADS The longer the connecting leads between the the ZoneMaster PLUS and power panel the higher the re...

Page 5: ...5 RECOMMENDED CABLE DRESSING...

Page 6: ...tic Connection Diagrams 6 120 240V SPLIT PHASE 3 W THREE PHASE 4W WYE THREE PHASE HIGH LEG DELTA NOTE L2 is designated as the HIGH LEG An optional breaker or disconnect may be used for overcurrent pro...

Page 7: ...from the counter and reinstalled to the ZoneMaster PLUS wire lug Note If it is desired to measure surge currents on only a single individual phase insert selected phase connection wire through the tor...

Page 8: ...lacement WARNING Before opening the access panel ensure that the AC supply has been disconnected Unplug the remote contact connector at the side of the module Remove the mounting screws on the module...