29
Fan fail
Fan abnormal
Check if the fan is running
Battery over voltage
Battery is over
charged
Switching to battery mode
automatically, and after the
battery voltage is normal
and the mains is normal, the
UPS would Switching to line
mode automatically again.
Battery low
Battery voltage is
low
When audible alarm
sounding every second,
battery is almost empty.
Charge fail
The charge is
broken
Notify dealer.
DC-DC temperature
high
Inside temperature
of the UPS is too
high
Check the ventilation of the
UPS, check the ambient
temperature.
Inverter temperature
high
Inside temperature
of the UPS is too
high
Check the ventilation of the
UPS, check the ambient
temperature.
Ambient temperature
high
The ambient
temperature is too
high
Check the environment
ventilation.
Line voltage high
(OVCD action)
Input power
voltage is too high
Switching to battery mode
automatically, and after the
mains is normal, the UPS
would Switching to line
mode automatically again.
Battery open
Battery pack is not
connected
correctly
Do the battery test to
confirm.
Check the battery bank is
connected to the UPS.
Check the battery breaker is
turn on.
Overload
Overload
Check the loads and
remove some non-critical
loads.
Check whether some loads
are failed.
Site fail
Phase and neutral
conductor at input
Rotate mains power socket
by 180° or connect UPS
Summary of Contents for VFI 1000T LCD
Page 38: ...35 DB 9 Interface of AS400 communication protocol...
Page 40: ...37 Appendix Rear panel PowerWalker VFI 1000T LCD PowerWalker VFI 1000T LCD L...
Page 41: ...38 PowerWalker VFI 2000T LCD PowerWalker VFI 2000T LCD L...
Page 42: ...39 PowerWalker VFI 3000T LCD PowerWalker VFI 3000T LCD L...
Page 43: ...40 614...