7. Trouble Shooting
If the UPS system does not operate correctly, first check the operating
information on the LCD display.
Please attempt to solve the problem using the table below. If the
problem still persists, consult your dealer.
7.1 Trouble Shooting According To Warning Indication
Problem Displayed
Possible cause
Remedy
Read EEPROM Error
UPS internal fault
Consult dealer.
Epo Active
EPO connector is
closed
Check the EPO connector
status
On Maintain Bypass
Maintain bypass
switch is open
Check the maintain bypass
switch status
IP softstart failed
UPS internal fault
Consult dealer
Site Wiring Fault
Phase and neutral
conductor at input of
UPS system are
reversed
Reverse mains power wiring.
Battery Disconnect
Battery pack is not
connected correctly
Do the battery test to confirm.
Check the battery bank is
connected to the UPS.
Check the battery breaker is
turn on.
Battery low
Battery voltage is low
When audible alarm sounding
every second, battery is almost
empty.
Output Overload
Overload
Check the loads and remove
some non-critical loads.
Check if some loads are failed.
Fan Failure
Fan abnormal
Check if the fan is running
normally.
Charger Fail
The charge fails
Consult dealer.
Battery Over Voltage
Battery voltage is
higher than normal
value
Check if the battery quantity is
right.