18
EN
14: reserved
Interface
Setting
reserved
15: Inverter voltage calibration
Interface
Setting
Parameter 2:
you may choose
Add
or
Sub
to calibrate inverter
voltage
Parameter 3:
The voltage setting range is from 0V to 6.4V. The
default value is 0V.
16: Floating charger voltage adjustment
Interface
Setting
Parameter 2:
you may choose
Add
or
Sub
to adjust floating
charger voltage.
Parameter 3:
the voltage range is from
0V to 6.4V
, the default
value is 0V.
17: Constant charger voltage adjustment
Interface
Setting
Parameter 2:
you may choose
Add
or
Sub
to adjust constant
charger voltage.
Parameter 3:
the voltage range is from
0V to 3.2V
, the default
value is 0V.
18: Maximum charger current setting
Interface
Setting
Parameter 3:
The maximum charging current could be adjusted.
Default value is 4A for long run model and 1A for standard model.
The available options are 1A, 2A, 4A and 6A.
6A is only available for the UPS with 16 pieces of batteries.