The following steps refer to bottom feed installations only.
Once the UPS has been properly unpacked (see page 9) and placed in its installation location,
the leveling feet must be lowered. These levelers are located in the front of the unit below the
door.
POWERVAR recommends the following overcurrent device (provided by customer) to be used
as the electrical
supply
(input)
to
the 3200 Series UPS:
UPS Model
(kVA)
External
Overcurrent
Protection*
Recommended
Wire Size
Terminal Wire
Range
(Min. – Max.)
Tightening
Torque
(Min. – Max.)
10
35A
#8 AWG
#16 to # 0
AWG**
2.8 Nm (min) /
3.0 Nm (max)
20
70A
#4 AWG
#16 to # 0
AWG**
2.8 Nm (min) /
3.0 Nm (max)
30
110A
#1 AWG
#1 AWG to**
350 kcmil
#1 to 350 = 375
In-lbs.
40
150A
#2/0 AWG
#2/0 AWG to**
350 kcmil
#1/0 to 350 = 375
In-lbs.
Gnd. (All
models)
#6 AWG
#6 -2/0 AWG**
120 In-lbs.
* To be provided by customer ** 75°C min. rated CU conductors only
The terminals for input and output connections to the UPS are accessed by opening the hinged
front door of the UPS (Fig.2.6) Firmly grab the left hand side of the door and pull outward. The
magnetic keepers will release and the door will open exposing the flat front of the UPS (Fig.2.7).
Summary of Contents for 3200 Series
Page 1: ...1 A55 00033 Rev E December 2015 3200 Series User s Manual ...
Page 2: ...2 A55 00033 Rev E December 2015 ...
Page 5: ...5 A55 00033 Rev E December 2015 1 Introduction and Safety ...
Page 10: ...10 A55 00033 Rev E December 2015 2 Installation ...
Page 20: ...20 A55 00033 Rev E December 2015 3 Product Specifications ...
Page 23: ...23 A55 00033 Rev E December 2015 4 Operation ...
Page 50: ...50 A55 00033 Rev E December 2015 Fig 4 49 Fig 4 50 Fig 4 51 Fig 4 52 Fig 4 53 ...
Page 80: ...80 A55 00033 Rev E December 2015 Fig 4 127 ...
Page 81: ...81 A55 00033 Rev E December 2015 5 Maintenance ...
Page 98: ...98 A55 00033 Rev E December 2015 6 Warranty ...
Page 101: ...101 A55 00033 Rev E December 2015 7 Service and Troubleshooting ...
Page 103: ...103 A55 00033 Rev E December 2015 ...
Page 104: ...104 A55 00033 Rev E December 2015 ...
Page 105: ...105 A55 00033 Rev E December 2015 ...
Page 106: ...106 A55 00033 Rev E December 2015 ...
Page 107: ...107 A55 00033 Rev E December 2015 8 Drawings ...
Page 108: ...108 A55 00033 Rev E December 2015 POWERVAR 3200 Series 10 20kVA Dimensions ...
Page 109: ...109 A55 00033 Rev E December 2015 POWERVAR 3200 Series 30 40kVA Dimensions ...
Page 110: ...110 A55 00033 Rev E December 2015 ...
Page 111: ...111 A55 00033 Rev E December 2015 ...
Page 112: ...112 A55 00033 Rev E December 2015 ...
Page 113: ...113 A55 00033 Rev E December 2015 ...
Page 114: ...114 A55 00033 Rev E December 2015 ...
Page 115: ...115 A55 00033 Rev E December 2015 ...
Page 116: ...116 A55 00033 Rev E December 2015 ...
Page 117: ...117 A55 00033 Rev E December 2015 ...