119
A55-00033 Rev. E December 2015
Facility Data Planning Guide - 3200 Series
10 - 40kVA UPS (208V input, 208V output)
Power
Rating
UPS AC Input (208V)
Battery System
AC Output (208V)
Mechanical Information (UPS only)
Voltage
kW
Current
Min. Input
AWG
(includes
Neutral)
External
Overcurrent
Protection
Current
Nominal
Minimum
Output
AWG
External
Overcurrent
Protection
Dimensions
W x D x H
Weight
lbs.
Floor
Loading
lbs. /
sq. in.
Heat
Rejection
kBTU /
Hr.
Cooling
Air
CFM
Nominal
Voltage
Maximum
Discharge
kVA kW
VAC
Nom. Max. Nom. Max.
10
9
208
10
10
28
36
8
35
216 (x2)
25.8A
28
10
30
18 x 34 x
48
850
1.11
3.79
480
20
18
208
20
20
56
68
4
70
216 (x2)
51.6A
56
6
60
18 x 34 x
48
951
1.29
7.6
480
30
27
208
30
30
83
103
2
110
216 (x2)
77.4A
83
4
90
23.2 x 34 x
60
1490
1.7
9.1
898
40
36
208
40
40
111
136
1/0
150
216 (x2)
103A
111
1
125
23.2 x 34 x
60
1555
1.72
12.1
898
Notes:
1
2
3,4,8,10,A,B,C
4,7, 11
5, 12
6,10
1
4,7,11
9
Notes:
1. Nominal (Nom.) current based on rated load.
12. 432VDC with Neutral
2. Maximum (Max.) current based on -15% input voltage
* Calculation based on ambient operating temperature of 25C
3. Input and output cables typically run in separate conduits.
4. If initial load is less than UPS rated output, it is recommended that AC input, battery, and AC
output wiring and overcurrent protection be sized to UPS full load rating to accommodate possible
Additional Notes:
future expansion.
A. Ratings of cables and overcurrent devices supplied for information only. User to consult with
5. Nominal battery voltage - (lead technology) (2.0 volts/ cell, cutoff 1.7 volts/cell)
it's engineering services before adopting.
6. If user provided DC cables should be sized for not more than a 2.0% line drop at maximum
B. Reference NEC handbook. Consult local codes for possible variations.
discharge current.
C. For site configurations including emergency generators to be sized and equipped for UPS
7. Suggested AC output overcurrent protection based on continuous full load current per NEC 210-20.
applications. Generator equipped with governor for frequency regulation and regulator for voltage
8. All wiring to be in accordance with the applicable national and/or local electrical codes.
stability recommended. Note: UPS reflected current distortion is 3% max at full load, and 5% at
(Conductor sizes based on 75 degrees C)
50% load
9. Minimum access clearance per UPS Owner's Manual
10. Control wiring and power wiring to be run in separate conduit.
Terminal conductor range:
10/20kVA -12 to #6 AWG
30/40kVA - #6 to 350kcmil
11. Nominal output current based on matching AC input / output voltages
Summary of Contents for 3200 Series
Page 1: ...1 A55 00033 Rev E December 2015 3200 Series User s Manual ...
Page 2: ...2 A55 00033 Rev E December 2015 ...
Page 5: ...5 A55 00033 Rev E December 2015 1 Introduction and Safety ...
Page 10: ...10 A55 00033 Rev E December 2015 2 Installation ...
Page 20: ...20 A55 00033 Rev E December 2015 3 Product Specifications ...
Page 23: ...23 A55 00033 Rev E December 2015 4 Operation ...
Page 50: ...50 A55 00033 Rev E December 2015 Fig 4 49 Fig 4 50 Fig 4 51 Fig 4 52 Fig 4 53 ...
Page 80: ...80 A55 00033 Rev E December 2015 Fig 4 127 ...
Page 81: ...81 A55 00033 Rev E December 2015 5 Maintenance ...
Page 98: ...98 A55 00033 Rev E December 2015 6 Warranty ...
Page 101: ...101 A55 00033 Rev E December 2015 7 Service and Troubleshooting ...
Page 103: ...103 A55 00033 Rev E December 2015 ...
Page 104: ...104 A55 00033 Rev E December 2015 ...
Page 105: ...105 A55 00033 Rev E December 2015 ...
Page 106: ...106 A55 00033 Rev E December 2015 ...
Page 107: ...107 A55 00033 Rev E December 2015 8 Drawings ...
Page 108: ...108 A55 00033 Rev E December 2015 POWERVAR 3200 Series 10 20kVA Dimensions ...
Page 109: ...109 A55 00033 Rev E December 2015 POWERVAR 3200 Series 30 40kVA Dimensions ...
Page 110: ...110 A55 00033 Rev E December 2015 ...
Page 111: ...111 A55 00033 Rev E December 2015 ...
Page 112: ...112 A55 00033 Rev E December 2015 ...
Page 113: ...113 A55 00033 Rev E December 2015 ...
Page 114: ...114 A55 00033 Rev E December 2015 ...
Page 115: ...115 A55 00033 Rev E December 2015 ...
Page 116: ...116 A55 00033 Rev E December 2015 ...
Page 117: ...117 A55 00033 Rev E December 2015 ...