User manual 6/10 kVA Rev.2
3. Operation
3.2 Starting up/ Shutting down the UPS
Starting up of the UPS
Step 1. Connect the UPS into an AC mains supply and the UPS will enter Bypass mode.
Step 2. Press the “Select-down” & “Enter” buttons simultaneously to switch on UPS.
The UPS will begin its start-up process. After entering the Normal Mode, the UPS is
ready for operation.
Shutting down the UPS
Press the “Select-up” & “Select –down” buttons simultaneously for a few seconds. The UPS
will Turn off.
During shutdown, do not press any buttons. Pressing a button may
cause the UPS to re-energize and deliver output power.
Battery Start-up of the UPS
Step 1: Unplug the UPS from any AC mains supply.
Step 2: Press the “Select-down” & “Enter” buttons simultaneously to switch on UPS. The
UPS will begin its start-up process. After entering the Battery Mode, the UPS is ready for
operation.
POWERTRONIX . - Page 16 of Total 29 - January 2006