POWERDIST AUST PTY LTD
6/14
DONE BY: CDP / JHI
REV 1
DATE: 01/05/12
2 TERMINAL BLOCK CROSS REFERENCES
TERMINAL
DECS125-15
TERMINAL
DECS200
REMARKS
POWER INPUT
-
C1
(GND)
To be connected to the chassis ground.
A
C2
(A)
B
C3
(B)
C
C4
(C
)
FIELD OUTPUT
F+
C5
(F+)
F-
C6
(F-)
VOLTAGE
SENSING
E1
A1
(E1)
E2
A2
(E2)
E3
A3
(E3)
BUS SENSING
BUS1
A4
(B1)
BUS3
A5
(B3)
CURRENT
SENSING
CTB1
B1
(CTB 1A)
CTB1 has to be connected on B1 or
B2
(CTB 5A)
B2 as per your droop CT secondary.
CTB2
B3
(CTB COM)
CROSS CURRENT
COMPENSATION
B4
(CTCC 1A)
A dedicated CT is recommended for
B5
(CTCC 5A)
the CCC with the DECS200. Please refer
B6
(CTCC COM)
to chapter 3.2 for more details.
PARALLELING
CONTROL
52L
A35
(52L/M)
52M
A36
(COM)
VAR/PF
CONTROL
52J
A37
(52J/K)
52K
A38
(COM)
EXTERNAL
ADJUST
6U
A29
(RAISE)
7
A30
(COM)
6D
A31
(LOWER)
AUX. ADJUST
(Biasing)
A8
(GND)
Accessory input can be a
A
A9
(V+)
4-20mA signal if preferred. Refer to
chapter 3.2
B
A10
(V-)
for more details.
ALARM
ALRM-
A15
Relay 1
3 programmable output relays are
ALRM+
A16
available if required.
AUXILIARY
POWER SUPPLY
B7
BATT+
An auxiliary power supply is required
B8
BATT-
with the DECS200, refer to the
B9
L
chapter 3.3 for more details.
B10
N
START / STOP
A21
START
A start / stop signal is required
A22
with the DECS200, refer to the
A23
STOP
chapter 3.3 for more details.
A24