Installation and Operator’s Manual
Page 75 of 108
(PVI-3.0/3.6/4.2-OUTD-x-US Rev: 2.1)
5.5.7.7
Language
It is possible to set the national language or English.
5.5.7.8
Start-up Voltage
Start-up voltage can be set according to the available photovoltaic system. Voltage
range can be 120V to 350V. Default setting for Aurora is 200V. This parameter can be
changed by means of the display keys.
5.5.7.9
Autotest
This is the Aurora inverter's internal test for checking correct operation of the
protection and the grid interface device, as provided for by UL 1741 regulation.
Press ENTER to access all information of this section:
OV = Max. voltage
UV = Min. voltage
OF = Max. Frequency
UF = Min. Frequency
DC injection = Output current direct component. This component shall not be >0.5%
with respect to inverter maximum rated current or the unit will switch off.
OV test
UV test
OF test
UF test
DC injection
Autotest
VStart
200V
English
Italiano