3. selection of installation location
The installation location of the AURORA inverter must be chosen taking in account the followings:
4. Wall mounting
The AURORA inverter should be mounted vertically, with a maximum inclination from the vertical of 5°. Any
larger inclination from the vertical could reduce the power conversion capability with a consequent reduction
in energy harvesting.
To correctly wall mount the inverter, follow the following procedure:
note: In the PVI-10.0/12.5-TL-OUTD models the support bracket only permits the upper part of the inverter to be
secured through the procedure previously described; to secure the lower part of the inverter, in the absence of the
PEM M6, you must make additional holes in line with the slot in the inverter’s lower flange (det. [E]), and then use
the SX10 dowels and 6.3x70 screws to secure the part to the wall.
Drill Ø 10 mm holes to a depth of 75 mm in line with the support bracket’s fixing holes (det. [a])
Secure the inverter’s support bracket using the SX10 dowels and 6.3x70 screws provided. The inverter’s spring
hook (det. [B]) must be positioned at the top; the fixing PEM M6 (det. [c]) must be positioned at the bottom.
Hook the inverter to the bracket spring (det. [B]) by the screw holes in the bracket on the back of the
inverter (det. [d]). Secure the lower part of the inverter to the PEM M6 on the bracket (det. [c]) using the
M6x10 screw, the D.18 washer and the slot in the inverter’s lower flange (det. [e]).
Choose a location sheltered from direct sunlight or other sources of heat.
Choose a well ventilated place so as to allow good circulation of air around the unit; avoid places where air
cannot circulate freely around the unit.
Choose a place with sufficient space around the unit to permit easy installation and removal of the object
from the mounting surfaces.
If more than one unit is installed, avoid placing one unit above the other so as to prevent overheating of
the unit installed above through the heat given off by the one below. Some examples of multi-inverter
installations are shown in the picture below.
minimum clearances around the unit.
*3-way terminal board counterparts (ALARM): 2 pieces; 8-way terminal board counterparts (signals): 2 pieces.
**Per the PVI-10.0/12.5-TL-OUTD-S models: 4 pieces; for the PVI-10.0/12.5-TL-OUTD and PVI-10.0/12.5-TL-OUTD-FS models: 6 pieces.
Summary of Contents for Aurora PVI-10.0-TL-OUTD
Page 31: ......
Page 64: ...Photovoltaic Inverters APPENDIX B Cable wiring diagram for RS485 line...
Page 69: ...Photovoltaic Inverters...