background image

Information on Fuel/Air Modes of Operation for Combination Gas/Oil Units (also see Section 3, page 15)

General Information
Specific adjustments and mechanical operation of the 

various modes of fuel/air control for straight gas and 

straight oil burners are included in this manual. This 

information should be used to properly adjust each fuel  

for combination gas/oil units. The following information  

is offered as additional guidance.

Gas On/Off System Combined with Oil On/Off System
The air dampers are adjusted and locked in place for the 

most efficient operation for both fuels. Refer to the  

mechanical operation of the Gas On/Off and Oil On/Off 

systems for adjustment details (pages 15, 16 and 17).

4.

 

GENERAL START UP PROCEDURES-ALL FUELS

All Fuels - General Start Up

A thoroughly qualified burner technician should be 

employed to provide the initial burner start up, as well as 

any subsequent servicing.

A representative of the owner and/or the person or persons 

responsible for operating and maintaining the unit 

should be present during the initial start up.  A service 

representative may also be required by the local utility 

on gas fired equipment. Instructions regarding the 

proper care and maintenance of the unit should be 

outlined with these people present.

Before beginning start up, the start up technician should 

thoroughly study and become completely familiar with 

the exact sequence of operation and all other details of 

the specific flame safeguard control system being used. 

This information will be found in bulletins printed and 

supplied by Honeywell or  Fireye. A copy of this bulletin 

was supplied with the burner.

After the burner is mounted and all wiring and piping has 

been completed, tested and determined to be correct, 

the following procedures are recommended:

For combination gas/oil units; the gas side operation 

should be set up first to clock the gas meter, allowing 

precise gas inputs to be determined. Once the gas ope-

ration is complete, the oil side can be set up easily by 

correlating the CO

2

 values of the two fuels. See page 

41, Table 13, CO

2

-O

2

 Ratio Curves for Fuel Oils and 

Gases

If it is anticipated that the Gas/Oil burner will rarely run on 

oil; it is recommended that the blower motor driven oil 

pump drive coupling be removed - and replaced only 

when required for oil firing. If, however, the pump coupling 

is left connected to the blower motor, it is essential to 

ensure that the pump has a good oil supply, when the 

burner is operating on the gas cycle, so that it will not 

run dry.  Be certain on initial start up that the pump is 

adequately primed to prevent against mechanical seizure 

caused by lack of oil. The pump warranty will be voided 

if the pump is run without adequate oil supply.

1.  Make a general inspection tour of the equipment room  

  to ensure that the installation is complete. Check piping,  

  controls, and wiring. When using the Alpha System™  

  Circuit Board, check wiring connections before power- 

  ing the unit. See page 7 & 8 for connection diagram.

  NOTE: L1 Main 115 volt hot incoming power terminal  

  is located on the lower set of terminals at the bottom  

  of the main circuit board. The L1 Fused terminal  

 

  located on the lower set of terminals is for factory    

  use only and should not be used for incoming power  

 connections.

2.  Close main and checking gas cocks. Open suction  

  line manual oil valves and others as appropriate.

3.  Tighten all screws on terminal blocks in control cabinet  

 in 

case some may have loosened in shipment.

4.  Do not secure flame safeguard control into its wiring base  

  until it has been determined that there are no shorts or  

  grounds in the system.

5.  Check fuses in main panel and in burner control cabinet.  

  Check wiring to the burner control cabinet for compliance  

  with the wiring diagram and local codes. Determine that   

  voltage supply is correct to motor starter line connections  

  and to control circuit line connections. If a control circuit   

  transformer is supplied, make certain its primary voltage  

  matches the line voltage being supplied. (A 230 volt  

  transformer does not produce proper control voltage when  

   supplied with 208 volts.)
6.  Check breaching and stack to ensure that they are open  

 

and unobstructed.

7.  Check blower (and oil pump motor, as applicable) rotation  

 

by momentarily making contact of the motor starters. Proper  

 

rotation is imprinted on the fan housing and (if supplied)  

 

the remote oil pump set assembly.

 8.  Check operating controls, limit controls, low water cut-off,  

 

flame safeguard control reset, high and low gas pressure  

 

switches (if used) and low fire interlock switch (if used) and  

 

all other applicable interlocks. All contacts should be closed  

 

(an exception will be found on jobs using the low gas  

 

pressure switch; this switch should be open until the main  

 

gas cock is opened). If a low oil pressure switch is used,  

 

its contacts will remain open until the oil pump is running  

 

and the low oil pressure cut-in point is reached.

9.    Do not repeatedly recycle the burner, so as to allow any  

       unburned fuel in the combustion chamber.
10.  Specific instructions relative to component sequencing  

       are provided in the flame safeguard manufacturer’s bulletin  

      which is included with the documentation shipped with the 

       burner. Refer to Honeywell and Fireye literature regarding  

       the clipping of jumpers or setting of DIP switches in     

       connection with the pilot establishing period, flame failure  

       action, and air flow switch failure features.
11. Proper test equipment must be used in order to achieve  

       maximum system operational reliability and fuel efficien- 

       cies. See page 24 for equipment lists.
12.  All fuel/air adjustments should be made to achieve required  

       input rate, satisfactory combustion test values, flame  

       stability and appearance.
13.  Every new burner start up should employ the use of the  

      Burner Start Up Information and Test Data sheets on     

      pages 46 and 47.

Gas On/Off System with Oil On/Off Fixed Air Low Fire Start 
System
The air dampers are adjusted and locked in place for the 

most efficient high fire operation for both fuels. Smooth light 

off on gas is achieved by the use of a slow opening diaphragm 

or motorized gas valve, which, once energized, allows gas 

flow to steadily increase from the initial light off volume up 

to the high fire volume. Smooth light off on oil is achieved by 

the use of a solenoid oil valve bypass system which allows 

a reduced amount of oil to be burned at light off and then 

switching to the high fire rate once the low fire has been 

established. Refer to the mechanical operation of the Gas 

On/Off system and the Oil Fixed Air Low Fire Start system 

C23

Rev.304

Summary of Contents for C1-GO-10

Page 1: ...C MANUAL POWER FLAME INCORPORATED...

Page 2: ...6 Removable Total Access Door 27 Optional Board for Sequence Indicator Lights The computer generated Burner Specification Sheets shipped with the burner represent the as built version of your specific...

Page 3: ...fore starting up the system all appropriate air and oil leak tests should be performed Make certain that the tank atmospheric vent line is unobstructed Refer to page 12 Figure 11 for fuel pump oil pip...

Page 4: ...valves etc Suction line vacuum values for such compo nents vary by manufacturer A Rule of Thumb to determine total vacuum for suction line sizing is to add 10 to vacuum determined from Figure 10 calcu...

Page 5: ...r calls for low fire the normally closed Oil Solenoid Return Valve 7 closed at high fire is energized reducing nozzle pressure to the low fire rate Simultaneously the Three Way Solenoid Valve 10 is de...

Page 6: ...trol Mode Using a Two Step Oil Pump Model C O Field Piped Check Valve At Tank Fuel Shutoff Valve Fusible Link Valve If Required by Code Check Valve Field Piped 12 pressure setting of the pump low fire...

Page 7: ...urn Pressure Tap 8 5 Metering Valve 7 1 8 Allen Screw For Oil Nozzle Pressure Adjustment Under Cap Vacuum Gauge Inlet Port Optional Return Port For Simplex Nozzle Use Alternate Connec tion to Tee on O...

Page 8: ...us tion chambers or high heat release pressurized fireboxes Moving the adjustment knob back increases the premix air Gas Oil Linkage Adjustment For Full Modulation Standard System Typical general link...

Page 9: ...als is for factory use only and should not be used for incoming power connections 2 Close main and checking gas cocks Open suction line manual oil valves and others as appropriate 3 Tighten all screws...

Page 10: ...uit the particular operating conditions 3 Do not secure flame safeguard control into its wiring base until it has been determined that there are no shorts or grounds in the system 4 Install oil pressu...

Page 11: ...chamber 18 For small On Off burners with a simplex nozzle adjustments consist primarily of attaining correct fuel air ratios Adjustments should be set to obtain11 121 2 CO2 and no more than a 2 smoke...

Page 12: ...rm in the boiler or follow specific initial firing recommendations provided by the heat exchanger manufacturer 34 Tighten all linkages and permanently mark settings 35 Limit control check should be ma...

Page 13: ...sure gauges overhead oil lines or fittings A leaking check valve on the bypass return line from the nozzle can create the same effect 6 The Teflon seal should stay on the nozzle when servicing On some...

Page 14: ...2 Fuel Oil By Pass Return Closed Approx High Fire Rate GPH 300 PSIG By Pass Return Closed Approx High Fire By Pass Return Pressure PSIG By Pass Return Closed Approx By Pass Return Pressure PSIG Appro...

Page 15: ...eturn and Firing Rates Will be Reduced Somewhat Consult Factory for Further Information When Supply Pressure to Nozzle is Lower Than 300 PSIG the By Pass Return and Firing Rates Will be Reduced Somewh...

Page 16: ...lon seal in the Monarch F80BPS and Delavan 33769 nozzles is an integral part of the nozzles and that if the seal is removed accidentally the nozzle must be replaced On the Delavan 30630 and 30637 nozz...

Page 17: ...ulators should be kept clean and must be replaced if cracked 2 The spark gap must be set in accordance with the dimensions noted Refer to Figures 30 31 32 Ensure that the distance between the electrod...

Page 18: ...Setting 1 16 Blade Tips After Adj Must be Within 1 16 of A Flat Plane Mark Pipe With Saw For Full Forward Pilot Extends Thru Diffuser 0 125 1 8 5 32 Diameter Orifice Gas Inlet Oil Nozzle Choke Assembl...

Page 19: ...e or check valve not holding Correct as required GAS OPERATION 1 Burner Motor Runs but Pilot Does Not Light A Gas supply to burner shut off make sure all manual gas supply valves are open Automatic hi...

Page 20: ...echanical binding of linkage Readjust linkage O Loose wiring connections Check and tighten all connections 2 Oil Flame Ignites but then Flame Safeguard Control Locks Out on Safety A Flame scanner lens...

Page 21: ...f necessary F On two step pump N O pump mounted oil solenoid valve defective not closing Replace valve or pump G Oil pump coupling loose slipping or defective Replace H Linkage mechanically binding Re...

Page 22: ...turer s instructions Refractory hold in As required annually Service Technician See Pilot turndown tests High limit safety control Annually Service Technician Refer to heat exchanger manufacturer s in...

Reviews: