DELAVAN VARI-FLO 30630 and 30637

Nozzle Size

300 PSIG 

Nominal 

Rating GPH 

#2 Fuel Oil 

By-Pass 

(Return) 

Closed

Model 

Number

Approx. 

High Fire 

Rate 

GPH 300 

PSIG 

By-Pass 

(Return) 

Closed

Approx. 

Alternate 

Nozzle 

Pressure 

PSIG

Approx. 

GPH

Approx. 

By-Pass 

(Return) 

Pressure 

PSIG 

Approx. 

Firing Rate 

GPH

Approx. 

By-Pass 

(Return) 

Pressure 

PSIG 

Approx. 

Firing Rate 

GPH

Supply Pressure to Nozzle 300 PSIG at All Rates Except Alternate Firing*

Alternate Firing

Approx. High 

Fire By-Pass 

(Return) 

Pressure  

PSIG 

By-Pass  

Return) 

Closed

Nozzle Data

 

35.0 

#30630 

35.0 157 -  - 140 

32.0 

100 

18.7

 

37.5 

#30630 

37.5 180 -  - 140 

28.6 

100 

13.8

 

40.0 

#30630 

40.0 191 -  - 140 

25.4 

100 

16.7

 

45.0 

#30630 

45.0 192 -  - 140 

30.6 

100 

16.5

 

50.0 

#30630 

50.0 

185 

- - - - 86 

16.7

 55.0 

#30630  55.0 

182 

91 

18.3 

-

 60.0 

#30630  60.0 

178 

94 

20.0 

-

 65.0 

#30630  65.0 

165 

85 

21.7 

-

 70.0 

#30630  70.0 

174 

88 

23.3 

-

 

80.0 

#30630 -  154 265  75  78 25.0  -  -

 80.0 

#30637 

260 

74 

85 

24.7 

-

 80.0 

#30637 

280 

78 

90 

26.0 

-

 80.0 

#30637  80.0 

157 

65 

27.0 

-

 90.0 

#30637 

260 

83 

90 

27.7 

-

 90.0 

#30637 

280 

86 

85 

28.7 

-

 90.0 

#30637  90.0 

165 

80 

30.0 

-

 

100.0 

#30637 -  136 260  93  90 31.0  -  -

 

100.0 

#30637 -  151 280  97  90 32.0  -  -

 100.0 

#30637  100.0 

165 

90 

32.3 

-

 

125.0 

#30637 -  161 260 115.0 90 38.0  -  -

 

125.0 

#30637 -  163 280 120.0 90 39.0  -  -

 125.0 

#30637  125.0 

175 

90 

41.0 

-

 

150.0 

#30637 -  161 260 140.0 90 45.0  -  -

 

150.0 

#30637 -  163 280 145.0 90 50.0  -  -

 150.0 

#30637  150.0 

175 

90 

56.0 

* When Supply Pressure to Nozzle is Lower Than 300 PSIG the By-Pass(Return) and Firing Rates Will be Reduced Somewhat.  

  Consult Factory for Further Information.

* When Supply Pressure to Nozzle is Lower Than 300 PSIG the By-Pass (Return) and Firing Rates Will be Reduced Somewhat.        

C

Consult Factory for Further Information.

  Nozzle Size 

  100 PSIG  Approx. High Approx. High 

 

Nominal 

Fire Rate  Fire By-Pass 

 

Rating 

GPH GPH  (Return) Approx. Approx.  Approx.  Approx. Approx. Approx. 

  #2 Fuel Oil 

300 PSIG 

Pressure 

By-Pass 

Firing Rate 

By-Pass 

Firing Rate 

By-Pass 

Firing Rate 

 

By-Pass 

By-Pass 

PSIG 

By-Pass 

(Return) GPH  (Return)  GPH (Return) GPH

 

(Return) 

(Return) 

(Return) 

Pressure   Pressure   Pressure  

 

Closed 

Closed 

Closed 

PSIG   PSIG   PSIG

 

4.5  7.5 162 120  5.0 100  4.0  70  3.0

 

5.0  8.5 136 120  7.0 105  6.0  75  4.0

 

5.5  9.2 150 130  8.0 120  7.0  80  4.0

 

6.0 

- - - - - - - -

 

6.5 10.8 160 160  9.0 120  7.0  80  4.0

 

7.0 12.0 141 125 10.0 110  8.0  67  4.0

 

8.0 13.0 158 130 10.0 120  8.0  85  5.0

 

9.0 15.0 132 100 10.0  90  7.5  60  5.0

 

9.5 15.0 158 120 10.0 110  7.5  80  5.0

 

10.0 

16.0 

150 

- - - - - -

 

12.0 20.0 154 118 16.0  94  12.0  70  8.0

 

14.0 23.0 160 120 17.0 100 11.0  85  8.0

 

16.0 26.0 144 115 17.0 100 15.0  75  10.0

 

18.0 30.0 165 135 22.0 110 15.0  80  10.0

 

20.0 32.0 160 120 24.0 100 18.0  80  14.0

 

22.0 36.0 155 120 27.0 100 20.0  82  15.0

 

24.0 41.0 144 120 30.0 100 25.0  72  15.0

 

26.0 43.0 150 100 35.0 100 27.0  65  15.0

 

28.0 47.5 148 120 40.0 100 30.0  65  16.0

 

30.0 51.0 138 85 40.0 75 30.0 50 17.0

 

35.0 60.0 175 115 40.0  90  30.0  60  20.0

 

40.0 68.0 115 70 45.0 50 35.0 20 23.0

 

45.0 76.0 166 120 60.0  85  40.0  50  25.0

 

50.0 

85.5 

- - - - - - - 

DELAVAN VARI-FLO 33769

Supply Pressure to Nozzle 300 PSIG at All Rates*

Reduced Firing Rates

C33

Rev.304

Summary of Contents for C1-GO-10

Page 1: ...C MANUAL POWER FLAME INCORPORATED...

Page 2: ...6 Removable Total Access Door 27 Optional Board for Sequence Indicator Lights The computer generated Burner Specification Sheets shipped with the burner represent the as built version of your specific...

Page 3: ...fore starting up the system all appropriate air and oil leak tests should be performed Make certain that the tank atmospheric vent line is unobstructed Refer to page 12 Figure 11 for fuel pump oil pip...

Page 4: ...valves etc Suction line vacuum values for such compo nents vary by manufacturer A Rule of Thumb to determine total vacuum for suction line sizing is to add 10 to vacuum determined from Figure 10 calcu...

Page 5: ...r calls for low fire the normally closed Oil Solenoid Return Valve 7 closed at high fire is energized reducing nozzle pressure to the low fire rate Simultaneously the Three Way Solenoid Valve 10 is de...

Page 6: ...trol Mode Using a Two Step Oil Pump Model C O Field Piped Check Valve At Tank Fuel Shutoff Valve Fusible Link Valve If Required by Code Check Valve Field Piped 12 pressure setting of the pump low fire...

Page 7: ...urn Pressure Tap 8 5 Metering Valve 7 1 8 Allen Screw For Oil Nozzle Pressure Adjustment Under Cap Vacuum Gauge Inlet Port Optional Return Port For Simplex Nozzle Use Alternate Connec tion to Tee on O...

Page 8: ...us tion chambers or high heat release pressurized fireboxes Moving the adjustment knob back increases the premix air Gas Oil Linkage Adjustment For Full Modulation Standard System Typical general link...

Page 9: ...als is for factory use only and should not be used for incoming power connections 2 Close main and checking gas cocks Open suction line manual oil valves and others as appropriate 3 Tighten all screws...

Page 10: ...uit the particular operating conditions 3 Do not secure flame safeguard control into its wiring base until it has been determined that there are no shorts or grounds in the system 4 Install oil pressu...

Page 11: ...chamber 18 For small On Off burners with a simplex nozzle adjustments consist primarily of attaining correct fuel air ratios Adjustments should be set to obtain11 121 2 CO2 and no more than a 2 smoke...

Page 12: ...rm in the boiler or follow specific initial firing recommendations provided by the heat exchanger manufacturer 34 Tighten all linkages and permanently mark settings 35 Limit control check should be ma...

Page 13: ...sure gauges overhead oil lines or fittings A leaking check valve on the bypass return line from the nozzle can create the same effect 6 The Teflon seal should stay on the nozzle when servicing On some...

Page 14: ...2 Fuel Oil By Pass Return Closed Approx High Fire Rate GPH 300 PSIG By Pass Return Closed Approx High Fire By Pass Return Pressure PSIG By Pass Return Closed Approx By Pass Return Pressure PSIG Appro...

Page 15: ...eturn and Firing Rates Will be Reduced Somewhat Consult Factory for Further Information When Supply Pressure to Nozzle is Lower Than 300 PSIG the By Pass Return and Firing Rates Will be Reduced Somewh...

Page 16: ...lon seal in the Monarch F80BPS and Delavan 33769 nozzles is an integral part of the nozzles and that if the seal is removed accidentally the nozzle must be replaced On the Delavan 30630 and 30637 nozz...

Page 17: ...ulators should be kept clean and must be replaced if cracked 2 The spark gap must be set in accordance with the dimensions noted Refer to Figures 30 31 32 Ensure that the distance between the electrod...

Page 18: ...Setting 1 16 Blade Tips After Adj Must be Within 1 16 of A Flat Plane Mark Pipe With Saw For Full Forward Pilot Extends Thru Diffuser 0 125 1 8 5 32 Diameter Orifice Gas Inlet Oil Nozzle Choke Assembl...

Page 19: ...e or check valve not holding Correct as required GAS OPERATION 1 Burner Motor Runs but Pilot Does Not Light A Gas supply to burner shut off make sure all manual gas supply valves are open Automatic hi...

Page 20: ...echanical binding of linkage Readjust linkage O Loose wiring connections Check and tighten all connections 2 Oil Flame Ignites but then Flame Safeguard Control Locks Out on Safety A Flame scanner lens...

Page 21: ...f necessary F On two step pump N O pump mounted oil solenoid valve defective not closing Replace valve or pump G Oil pump coupling loose slipping or defective Replace H Linkage mechanically binding Re...

Page 22: ...turer s instructions Refractory hold in As required annually Service Technician See Pilot turndown tests High limit safety control Annually Service Technician Refer to heat exchanger manufacturer s in...

Reviews: