SD750FR
POWER ELECTRONICS
72
MAINTENANCE
EN
MAINTENANCE
The SD750FR Series drives are industrial electronic products that contain advanced semiconductor
elements. For this reason, temperature, humidity, vibrations and worn components can affect performance.
To avoid any possible irregularities, it is recommended to carry out periodic inspections.
WARNING
Ensure to follow all instructions to safely carry out maintenance tasks.
Otherwise, you could cause damages to the equipment and personnel.
Warnings
Make sure to remove the input power while performing maintenance.
Make sure to perform maintenance after checking the DC Link capacitor has discharged. Check that the
voltage between terHVDC and -HVDC is below DC 30V. The bus capacitors in the drive main
circuit can still be charged even after the power is turned off.
The correct output voltage of the drive can only be measured by using an RMS voltage meter. Others
voltage meters, including digital voltage meters, are likely to display incorrect values caused by the high
frequency PWM output voltage of the drive.
Routine Inspection
It is necessary to perform periodic inspections of the drive. The frequency of the tasks shown in the table
below are recommended, the times indicated depend on the working conditions in each case.
Tasks with monthly recommendation must be performed, at least, every three months.
Make sure to check the following points before handling the drive:
•
Installation site conditions.
•
Drive cooling system conditions.
•
Excessive vibrations or noise in the motor.
•
Excessive overheating.
•
Normal output current value on the monitor.
12
Summary of Contents for SD750FR
Page 1: ...SD750FR HARDWARE AND INSTALLATION MANUAL 4Q REGENERATIVE ACTIVE FRONT END DRIVE...
Page 2: ......
Page 54: ...SD750FR POWER ELECTRONICS 52 POWER CONNECTION EN Connections for frame 6...
Page 55: ...POWER ELECTRONICS SD750FR POWER CONNECTION 53 Connections for frame 7...
Page 56: ...SD750FR POWER ELECTRONICS 54 POWER CONNECTION EN Connections for frame 8...
Page 79: ......