SD450 - DEVICENET
POWER ELECTRONICS
30
DEVICENET DATA TABLES
Implemented for:
Service Name
Service Code
Class
Instance
Get_attribute_Single 0x0E No Yes
Set_Attribute_Single 0x10 No Yes
Output Assembly Data Attribute Format
Instance
Bit
Byte
7
6
5
4
3
2
1
0
0
Fault
Reset
Run
Fwd
1
2
Speed Reference (Low Byte) – RPM
(Speed Reference (Low Byte) – Hz)
20
(100)
3
Speed Reference (High Byte) – RPM
(Speed Reference (High Byte) – Hz)
0
NetRef NetCtrl
Fault
Reset
Run
Rev
Run
Fwd
1
2
Speed Reference (Low Byte) – RPM
(Speed Reference (High Byte) – Hz)
21
(101)
3
Speed Reference (Low Byte) – RPM
(Speed Reference (High Byte) – Hz)
Related Attribute
Name
Description
Class
Attribute ID
Run Fwd
Forward Run Command
0x29
3
Run Rev
Reverse Run Command
0x29
4
Fault Reset
Fault Reset Command
0x29
12
NetRef
5
Not
Used
0x2A
4
NetCtrl
5
Not
Used
0x29
5
Speed Reference
Speed Command
0x2A
8
5
Setting Reference Control and Run/Stop Control only can be done from keypad.
Therefore, NetRef and NetCtrl in Instance 21 and 101 are not available.