POWER ELECTRONICS
SD300
DESCRIPTION OF PROGRAMMING PARAMETERS
183
Screen Description
Default
value
Range
Function
Set on
RUN
Communication
frame
structure
D8/PN/S
1
D8/PN/S1
D8/PN/S2
D8/PE/S1
D8/PO/S1
Select the communication frame
structure and defines the data length,
parity confirmation method and the
number of stop bits:
OPT DESCR. FUNCTION
0
D8 /
PN/S1
8-bit data / no parity
check / 1 stop bit
1
D8 /
PN/S2
8-bit data / no parity
check / 2 stop bits
2
D8/
PE/S1
8-bit data / even
parity / 1 stop bit
3
D8/PO/
S1
8-bit data / odd parity
/ 1 stop bit
YES
Response
delay
5ms
0 to 100 ms
The MODBUS-RTU communication
plays the role of the slave device. The
slave will reply after the time period set
in this parameter. This allows the
master
device
attending
the
communications within a system
where the master cannot manage a
quick slave answer.
YES
CM.6
[28]
Communication
option S/W
version
0.00
-
Show the software version of the
optional communications card, if there
is any connected.
YES
Communication
option ID
1
0 to 255
Identifier of the communications card
connected to the drive.
YES
Card baud
rate
12Mbps
-
Communications card baud rate.
YES
Communication
option LED
status
-
-
This parameter function depends on
the communications card.
YES
[28] Will only be displayed when a communications optional card is installed.
Summary of Contents for SD 300 Series
Page 1: ...SD300 GETTING STARTED MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE ...
Page 2: ......
Page 3: ...Variable Speed Drive Getting Started Manual Edition February 2019 SD30IM01GI Rev G ...
Page 159: ...POWER ELECTRONICS SD300 DESCRIPTION OF PROGRAMMING PARAMETERS 157 Power off delay ...
Page 174: ...SD300 POWER ELECTRONICS 172 DESCRIPTION OF PROGRAMMING PARAMETERS TI configuration ...
Page 352: ......
Page 353: ......