background image

General Precautions 

1. Before using 

Invisimo

, read all instructions and cautionary markings on : (1) 

Invisimo

 (2) 

the batteries (3) this manual 

2. 

CAUTION 

--To reduce risk of injury, charge only lead-acid type rechargeable batteries. 

Other types of batteries may cause damage and injury. 

3. Do not expose 

Invisimo

 to rain, snow or liquids of any type. 

Invisimo

 is designed for 

indoor. 

4. Do not disassemble 

Invisimo

. Take it to a qualified service center when service or repair is 

required. 

5. 

WARNING: 

Provide ventilation to outdoors from the battery compartment. The battery 

enclosure should be designed to prevent accumulation and concentration of hydrogen gas 

at the top of the compartment. 

6. 

NEVER 

charge a frozen battery. 

7. Be extra cautious when working with metal tools around batteries. Short-circuiting the 

batteries could cause an explosion. 

8. For battery installation and maintenance: read the battery manufacturer’s installation and 

maintenance instructions prior to operating. 

 

Personnel Precautions 

 

1. Have plenty of fresh water and soap nearby in case battery acid contacts skin, clothing, or 

eyes. 

2. Avoid touching eyes while working near batteries. 

3. Never smoke or allow a spark or flame in vicinity of a battery. 

4. Remove personal metal items such as rings, bracelets, necklaces, and watches when 

working with batteries. Batteries can produce a short-circuit current high enough to make 

metal melt, and could cause severe burns. 

5. If a remote or automatic generator start system is used, disable the automatic starting 

circuit or disconnect the generator to prevent accident during servicing. 

 

 

 

 

 

 

Specification 

MODEL 

Invisimo 700 

1000 

1500 

2000 3200 

CAPACITY 

VA / Watts 

700VA / 

450W 

1000VA / 

600W 

1500VA / 

900W 

2000VA / 

1200W 

3200VA / 

2000W 

AC Voltage 

115VAC / 230VAC, 1 Phase + Neutral 

Voltage Tolerance (AC) 

90~135VAC / 187~264VAC   

±

4% 

DC Voltage 

12VDC 

24VDC 

Voltage Tolerance (DC)

10VDC ~ 14VDC 

20VDC ~ 28VDC 

INPUT 

Frequency 

47Hz ~ 53Hz / 57Hz ~ 63Hz 

Voltage 

115VAC / 230VAC 

Voltage Tolerance 

±

7% 

Frequency 50Hz 

or 

60Hz 

Frequency Tolerance 

±

3Hz in Battery Mode 

Transfer Time 

Maximum 10 milliseconds 

OUTPUT 

Voltage Waveform 

Modified Sinewave 

Type 

Maintenance free dry type (suggested) 

Capacity 

Up to 1000Ah 

Battery Low Level 

10.8V   

±

0.2V 

21V  

±

0.5V 

Battery Cut-off Level 

10V   

±

0.2V 

20V  

±

0.5V 

BATTERY 

Battery house 

External; Rack or Cabinet (Optional) 

Battery Charge Voltage 

13.6VDC   

±

0.2VDC 

27.5V  

±

0.3V 

Charge Capacity 

40A max. (Adjustable) 

CHARGER 

Over Charge Protection

14.5VDC   

±

0.5VDC 

29V  

±

0.5V 

Control Panel 

On/Off button, Battery charge current adjustment 

Line Mode 

Line-On LCD lighting 

Battery Mode

Back-Up LCD lighting 

Over Load 

O-Load LCD lighting 

Over Temp. 

O-Temp LCD lighting 

UPS Off 

Cut-Off LCD lighting 

Load Level 

5-Step LCD lighting 

INDICATORS 
& CONTROL 
PANEL 

Indicators

Battery Level

5-Step LCD lighting 

Full Protection 

Over load, Short circuit, Over charge, Over temperature, Input 

& Output fuse 

Noise Level 

Less than 45 dBA (at 1 meter) 

Operating Temperature 

0

 ~ 40

 

Storage Temperature 

-20

 ~ +70

 

Relative Humidity 

Maximum 0-90% (non-condensing) 

Type of Cooling 

Forced with fan 

PROTECTION 

Installation Height 

<3000 meters, elevation 

Dimension, D*H*W 

420*160*218mm 

PHYSICAL 

Weight, w/o Battery 

9kgs 

11kgs 

14kgs 

16kgs 20kgs 

DESIGN, MANUFACTURE, SERVICES

ISO 9001 

Reviews: