Powered by Safety
®
31
IB-65020A
Installation
Figure 15 Push to Trip Knob & Racking Access
Window
a
b
a. Push to Trip Knob
b. Racking Access Window
a. Insert racking handle (Figure 16, b) into
the racking access window and turn
the racking handle clockwise until the
circuit breaker is fully racked into the
circuit breaker compartment. Once the
circuit breaker is fully connected, the
racking indicator flag (Figure 16, a) will
display
“CONNECTED”
.
b. Remove the racking handle and close
the racking access window.
Note:
This is the Connected Position
Once you have completed
steps a and b
, the
circuit breaker is ready to be operated.
Figure 16 Racking Indicator Flags & Racking
Handle
a
b
a. Racking Indicator Flags
b. Racking Handle
Note:
Compartment door is not shown for
visual aid.