Powered by Safety
®
17
Installation
01.4IB.65090A
d. Disconnect the remote control box
from the ground and test device.
When the electrical checks are
completed disconnect the secondary
disconnect plug from the ground and
test device
e. I
nSertInG
G
round
And
t
eSt
d
evIce
I
nto
S
WItchGeAr
e
quIpment
Refer to the appropriate instruction bulletin for
information and cautions before attempting to
insert a ground and test device into the
metal-clad switchgear equipment. The
information and cautions found in 01.4IB.65071
also apply to the ground and test device.
Ensure that the levering-in crank arms at the
sides of the device point in the direction of the
main disconnects.
Each ground and test device and each
compartment is provided, when required, with
an interference plate designed to ensure that
no device with less than the required voltage
or momentary current rating is placed in any
compartment. If attempting to insert an
improperly rated device into the switchgear,
these interference plates will interfere with
each other and deter the insertion of the
device. The interference occurs before the
device reaches the “DISCONNECT” position.
Do not force the device past the interference
plate or remove the interference plate from
the compartment or the ground and test
device.
!
CAUTION
Verify the correct ground and test device
is being inserted in the compartment of
the feeder to be grounded. Also, verify all
associated incoming and tie breakers are
open before inserting the ground & test
device. Failure to do so may result in damage
to equipment and/or injury to personnel.
!
CAUTION
1) Electrical Ground and Test Device Inspection
a. Inspect the primary disconnecting
devices for proper lubrication, damage,
debris, and dirt. Ensure that the
disconnecting devices are in alignment
and are not bent. If damage or dirt is
present, refer to
General Description, 2) Inspection and
.
If the primary disconnecting devices are
damaged, make no attempt to repair them.
Contact Powell for further information.
NOTICE
b. Inspect the switchgear compartment to
ensure that it is clean and clear of debris
that might interfere with ground and
test device travel.