Operating Procedures
01.4IB.50026A
31. Rotate key KC to lock the ground and test
device in the “Connected” position. Key KC
is now released.
32. Transfer key KC to key lock K2. Fully depress
the manual trip operator and rotate key KC.
Release the manual trip operator. Key KC is
now captive and key KB is now released.
33. Transfer key KB to key lock K1. Rotate key
KB. The ground and test device control
circuit is now enabled. Key KB is now
captive and the KCF key is released.
34. Remove the ground and test device from
the compartment.
35. Remove key KCF from key lock K1.
36. Secure key KCF in a lock box on premises.