B - Insert the Op cal Fibers
2 - Hardware Installa on
D - Typical Network Connec ons
C - Connect Network and Power Wiring
Star Topology (Ethernet)
Typical Serial Topology (MODBUS RTU)
(within cabinet) or connec ng with twisted pair cables (cabinet to cabinet)
I. Loosen the connectors by
screwing them counter
clockwise.
A - Mount on 35 mm DIN Rail
Installing
Removing
1
2
Input Voltage
Nega ve
Input Voltage
Nega ve
Input Voltage Posi ve
Input Voltage Posi ve
Inver ng, 2-wire, RS-
485
Chassis Grounding
Non-Inver ng, 2-wire,
RS-485
Shielding of
Communica on Pair
Relay:
Common Terminal
Relay:
Normally Open
Terminals 1-5
Terminals 6-10
Terminal
Terminal
Number
Number
Name
Name
Func on
Func on
6
V-
V-
Rx-
Shd
7
V+
V+
Tx+
8
PE
9
COM
10
NO
1
2
3
4
5
6
7 8 9 10
1
2
3
4 5
10/100
STAT
RST
ID#:
BriteSpot
G3
BS3
BS2
BS1
LINK COM SYS
4 5 6
7 8 9
1 2 3
10/100
STAT
RST
ID#:
BriteSpot
G3
BS3
BS2
BS1
LINK COM SYS
4 5 6
7 8 9
1 2 3
HMI
PLC
G3 Slave Device 1-31
10/100
STAT
RST
ID#:
BriteSpot
G3
BS3
BS2
BS1
LINK COM SYS
4 5 6
7 8 9
1 2 3
10/100
STAT
RST
ID#:
BriteSpot
G3
BS3
BS2
BS1
LINK COM SYS
4 5 6
7 8 9
1 2 3
HMI/Master
Hub
G3 Slave Devices
1
2
Note that terminals 1 and 6, as well as 2 and 7, are connected internally.
If a light remains red, ensure the probe is inserted
properly and the fiber cut is clean. Recut if necessary.
View LEDs above the connectors to determine if a
connec on has been established.
BS
3
BS
2
BS
1
7 8
1
III. Secure fiber reten on nuts
by screwing them clockwise.
BS
3
BS
2
BS
1
4
7 8
1
BS
3
BS
2
BS
1
4
7 8 9
1
II. Insert the op cal fibers
un l they come to a hard
stop. Do NOT apply excessive
force.
Quick Start Guide
G3
BriteSpot
Temperature Monitoring
Powell Canada Inc,
Suite 201, 55 Gos ck Place
North Vancouver, BC, V7M 3N2
Wiring Interface