
45
14.0 Fault Finding
Check and correct if necessary
1. Flame sensing electrode and lead connections
2. Flame sensing electrode position
Flame current should be 1 µA approx.
Replace main PCB
Replace main PCB
YES
YES
Replace flame sensing electrode
NO
YES
Ensure that mains input
terminal L is Live (230V) and
N is Neutral (0V)
I
Check terminal 1 of ON/OFF/RESET selector is in
connection with PCB - A4 connector terminal 2
Check electrical continuity across terminals 1 & a
on reset selector when turned to the reset position
Replace ON/OFF/RESET selector
NO
Replace main PCB
YES
K
Replace overheat
thermostat
YES
NO
Overheat thermostat operated
or faulty, i.e. continuity across
thermostat terminals
Allow to cool. Continuity
across thermostat terminals
more than 1.5 ohm
J
Check continuity of loop on
A10 connector
L
Replace main PCB
Is there 230V at:
Diverter valve operating head
Replace diverter valve operating head
1.
2.
PCB - A8 connector terminals
1 & 5 central heating function
1 & 3 DHW function
NO
M
Replace main PCB
YES
Change motor supply cable
YES
Fault Finding Solutions
Summary of Contents for Performa 28i
Page 47: ...16 0 Notes 47 ...