
7.0 Site Requirements
16
7.8
Flue
1.
The flue terminal position must be in
accordance with the current editions of B.S.
5440 Part 1, and either Part J of the Building
Regulations England and Wales or Part F of
the Building Standards (Scotland)
Regulations as appropriate.
2. If the terminal discharges onto a pathway or
passageway, check that combustion products will
not cause a nuisance and that the terminal will
not obstruct the passageway.
3. If a terminal is less than 2 metres above a
balcony, above ground or above a flat roof to
which people have access, then a suitable
terminal guard must be provided.
Terminal Position with Minimum Distance (Fig. 11)
(mm)
A
Directly below an openable window, air vent or any other
ventilation opening.
300
B
Below gutter, drain/soil pipe.
150
C
Below eaves.
200
D
Below a balcony/car port roof.
200
E
From vertical drain pipes and soil pipes.
150
F
From internal or external corners.
300
G
Above adjacent ground or balcony level.
300
H
From a surface facing a terminal.
600
I
Facing a terminals.
1200
J
From opening (door/window) in carport into dwelling.
1200
K
Vertically from a terminal on the same wall.
1500
L
Horizontally from a terminal on the same wall.
300
M Above an opening, air brick, opening window etc.
300
N
Horizontally to an opening, air brick, opening window etc.
300
L
G
G
E
J
D
K
G
A
A
D
F
H,I
B,C
F
Likely flue positions requiring
a flue terminal guard
M
N
Fig. 11
300 min
Terminal
Assembly
Top View Rear Flue
Property Boundary Line
NOTE:
Scotland Only - The distance from a
fanned draught appliance terminal installed at
right angles to a boundary may not be less
than 300mm in accordance with the diagram
below
Summary of Contents for Performa 28i
Page 47: ...16 0 Notes 47 ...