Mixing valve boost (830, 1130, 1430)
The heat request of the mixed heating circuit to the heat source is raised
above the value set here. This boost is intended to correct temperature
fluctuations to be able to be compensated with the mixer controller.
Actuator running time (834, 941, 1134)
Setting the actuator running time of the mixing valve used.
For mixing circuits, a kick-start of the mixer drive is carried out after a
pump kick-start (pump is OFF). In this case, the mixer is controlled in
direction OPEN and CLOSED.
The time of activation in direction OPEN corresponds to the drive running
time.
Floor curing function (850, 1150, 1450)
X Start day
Fh Functional heating
Ch Curing heating
The floor curing function serves controlled drying out of screed floors
Off: The function is switched off.
Functional heating: Part 1 of the temperature profile is run automatically.
Curing heating: Part 2 of the temperature profile is run automatically.
Functional/curing heating: The whole temperature profile is run
automatically.
Manually: Manual control to the screed setpoint.
Caution
Observe the requirements and standards issued by the screed
manufacturer.
A correct function is only possible with a correctly installed heating system
(hydraulic, electrical systems and settings).
Deviations can result in damage to the screed.
The screed function can be stopped prematurely by setting 0=OFF.
Floor curing setp manually (851, 1151, 1451)
Setting of the temperature to which manual control is carried out with floor
curing function activated.
For more information, see
Floor curing function (850, 1150, 1450), page 93
Floor curing setp current (855, 1155, 1455)
Display of the current floor curing setpoint.
Days completed.current (856, 1156, 1456)
Display of the current floor curing function day.
Excess heat draw (861, 1161, 1461)
If the excess temperature draw is activated via input H1 to H5 or a
maximum temperature is exceeded in the system, this excess heat energy
can be released by a heat draw of the room heating.
Off: The function is switched off.
Heating mode: The function is only limited to one draw-off during the
heating times.
Always: The function is generally released.
With buffer (870, 1170, 1470)
This parameter establishes whether the heating circuit can be supplied by
a buffer or storage tank or only by a heat generator. The function also
determines whether the system pump goes into operation when a heat
demand is submitted.
No: The heating circuit is supplied from the boiler.
Fig.26
Temperature profile of the floor
curing function
X
Fh
Bh
Fh + Bh
RA-0000072
9 Settings
7703046 - 01 - 23072018
Paramount five 30 – 115