AUTO TEST VSR (VSR-AT)

VANE TYPE WATERFLOW ALARM SWITCH WITH 

ELECTRONIC RETARD AND AUTO TEST FEATURE

MFG. #5401239 - REV B

3/14

Trouble Shooting Guide

A successful completion of the Auto Test will momentarily activate both sets of normally open contacts on the flowswitch for approximately 2 

seconds. 

If the Auto Test detects a problem with the trip stem/paddle assembly, or if there is no water in the pipe, neither normally open contact will 

operate. The flowswitch will then indicate a trouble condition at the ATC test switch and transmit a trouble signal to the fire alarm control 

panel.

When Fire Panel Stays in Trouble:

• 

Check the wiring

• 

The zone of the fire panel should be wired to the VSR-AT as 

shown on pg. 4 of bulletin 5401239. The End of Line Resistor 

should be installed as shown across the terminals marked C and 

the terminal to the right of C which is indicated by the other end 

of the resistor symbol. The zone of the fire panel connects to the 

terminals marked C and N.O.

• 

The NO and End of Line Resistor terminals are connected in-

ternally by a normally energized relay. A loss of power or failed 

AutoTest causes the relay to drop out and initiates a trouble at the 

fire panel.

• 

The only way to clear the trouble on the fire panel is to conduct 

a successful AutoTest using the ATC test switch or other test 

method. Conducting an actual waterflow test will put the panel in 

alarm but will not clear the trouble.

When VSR-AT Fails the Auto Test:

• 

Is there water in the pipe? The VSR-ST will fail the AutoTest if 

the pipe it is installed on is not full of water.

• 

Has the return spring on the VSR-AT been adjusted? This spring 

has been factory set and should not be adjusted  

 

in the field. Refer to Figure 8 to determine the factory spring 

setting. If the spring is not at the factory setting, turn the spring 

adjustment screw until the factory spring setting is restored.

• 

For other issues contact Potter Tech Support at 866-956-1211 

or visit our web site at http://www.pottersignal.com/ run your 

mouse over the FIRE SPRINKELR MONITORING header and 

select Tools and Resources. Click on presentations to select the 

VSR-AT Tech brief or troubleshooting video

Fig. 8 

Return Spring set 

to Factory Mark

Summary of Contents for VSR-AT Series

Page 1: ...The alarm contacts are actuated when a flow of 10 GPM 38 LPM or more occurs downstream of the device The flow condition must exist for a period of time necessary to overcome the selected retard time The VSR AT may be remotely tested without flowing water by using the optional auto test Control model ATC 1or ATC 4 or the use of addressable relays and monitor modules as part of a listed addressable ...

Page 2: ...d torque see the chart in Fig 1 The vane must not rub the inside of the pipe or bind in any way ADAPTER USE 2 5180162 ADAPTERS AS SHOWN ABOVE DN50 ONLY ADAPTER 50mm 20mm 2mm MAX DWG 1146 1F Fig 1 Compatible Pipe Installation Requirements Model Nominal Pipe Size Nominal Pipe O D Pipe Wall Thickness Hole Size U Bolt Nuts Torque Schedule 10 UL Schedule 40 UL BS 1387 LPC DN VDS inch mm inch mm inch mm...

Page 3: ...e inoperable risking severe property damage and loss of life Do not strip wire beyond 3 8 of length or expose an uninsulated conductor beyond the edge of the terminal block When using stranded wire capture all strands under the clamping plate Maintenance Inspect detectors monthly If leaks are found replace the detector The VSR AT waterflow switch should provide years of trouble free service Fig 4 ...

Page 4: ...te From power source suitable for bell 120 VAC connection shown See Note 1 Bell Orange ATC 1 Mounts to standard single gang handy or switch box 4 L X 2 1 8 W X 1 7 8 D such as RACO 660 or equivilent Box not included Black Blue The ATC consists of a momentary push button switch a key switch to enable disable the push button and an LED Turning the keyswitch to Test will enable the push button switch...

Page 5: ... contacts The connection to the waterflow zone of the fire panel involves 3 terminals on theVSR AT C and NO Connect the two wires fromthewaterflowzoneofthefirepaneltotheCandNOterminals with the End of Line Resistor of the fire panel being connected across the C and other terminal as shown on the drawing The NO and resistor terminal are internally connected by a normally energized relay Aloss of po...

Page 6: ... The NO and End of Line Resistor terminals are connected in ternally by a normally energized relay A loss of power or failed AutoTest causes the relay to drop out and initiates a trouble at the fire panel The only way to clear the trouble on the fire panel is to conduct a successful AutoTest using the ATC test switch or other test method Conducting an actual waterflow test will put the panel in al...

Reviews: