background image

PRINTED IN USA

 PAGE 3 OF 6

AUTO TEST VSR (VSR-AT)

VANE TYPE WATERFLOW ALARM SWITCH WITH 

ELECTRONIC RETARD AND AUTO TEST FEATURE

MFG. #5401239 - REV B

3/14

Removal of Waterflow Switch

•  

To prevent accidental water damage, all control valves should be shut tight and the system completely drained before waterflow detectors are  

 

 

 

 

removed 

or 

replaced. 

            

•  Turn off electrical power to the detector, then disconnect wiring.   

 

 

 

 

 

 

 

• 

 

Loosen 

nuts 

and 

remove 

U-bolts. 

           

•  Gently lift the saddle far enough to get your fingers under it.  With your fingers, roll the vane so it will fit through the hole while continuing  

    to lift the waterflow detector saddle.   

 

 

 

 

 

 

 

 

 

 

•  Lift detector clear of pipe.

To remove knockouts: Place screwdriver at inside edge of knockouts, not in 

the center.

DWG 1146-4

Fig. 2

Do not drill into the base as this creates metal shavings which can 

create electrical hazards and damage the device. Drilling voids the 

warranty.

Fig. 3   Switch Terminal Connections Clamping Plate Terminal

An uninsulated section of a single conductor should not be looped around the 

terminal and serve as two separate connections.  The wire must be severed, 

thereby providing supervision of the connection in the event that the wire 

become dislodged from under the terminal.  Failure to sever the wire may 

render the device inoperable risking severe property damage and loss of life.
Do not strip wire beyond 3/8" of length or expose an uninsulated conductor 

beyond the edge of the terminal block. When using stranded wire, capture all 

strands under the clamping plate. 

Maintenance

Inspect detectors monthly.  If leaks are found, replace the detector.  The VSR-AT waterflow switch should provide years of trouble-free service.

Fig. 4 Mounting Dimensions

DWG. 1146-14

3.50 in

 (89.0 mm)

2.34 in

 (59.4 mm)

PIPE DIA.

+ 5.25 in

 (+ 133.4 mm)

5.56 in

 (141.2 mm)

2.00 in

 (50.8 mm)

U-BOLT NUT

U-BOLT WASHER

PIPE SADDLE

PIPE

PLASTIC PADDLE

U-BOLT

NOMINAL PIPE DIA. +1.75 in (+44.5 MM) FOR DN 50 – DN 65 2–2.5 in

NOMINAL PIPE DIA. +2.125 in (+54.0 MM) FOR DN 80 – DN 200 3–8 in

Fig. 5

GREEN GROUND 

SCREWS

Testing 

 

          

The frequency of inspection and testing for the Model VSR-AT and  its associated protective monitoring system shall be in accordance with applicable 

NFPA Codes and Standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently).
An inspector’s test valve shall be provided for commissioning and test purposes when required by the AHJ. If there are no provisions for testing 

the operation of the flow detection device on the system, application of the VSR-AT is not recommended or advisable.

A minimum flow of 10 GPM (38 LPM) is required to activate this device.

Advise the person responsible for testing of the fire protection system that this system must be tested in accordance 

with the testing instructions.

Summary of Contents for VSR-AT Series

Page 1: ...The alarm contacts are actuated when a flow of 10 GPM 38 LPM or more occurs downstream of the device The flow condition must exist for a period of time necessary to overcome the selected retard time The VSR AT may be remotely tested without flowing water by using the optional auto test Control model ATC 1or ATC 4 or the use of addressable relays and monitor modules as part of a listed addressable ...

Page 2: ...d torque see the chart in Fig 1 The vane must not rub the inside of the pipe or bind in any way ADAPTER USE 2 5180162 ADAPTERS AS SHOWN ABOVE DN50 ONLY ADAPTER 50mm 20mm 2mm MAX DWG 1146 1F Fig 1 Compatible Pipe Installation Requirements Model Nominal Pipe Size Nominal Pipe O D Pipe Wall Thickness Hole Size U Bolt Nuts Torque Schedule 10 UL Schedule 40 UL BS 1387 LPC DN VDS inch mm inch mm inch mm...

Page 3: ...e inoperable risking severe property damage and loss of life Do not strip wire beyond 3 8 of length or expose an uninsulated conductor beyond the edge of the terminal block When using stranded wire capture all strands under the clamping plate Maintenance Inspect detectors monthly If leaks are found replace the detector The VSR AT waterflow switch should provide years of trouble free service Fig 4 ...

Page 4: ...te From power source suitable for bell 120 VAC connection shown See Note 1 Bell Orange ATC 1 Mounts to standard single gang handy or switch box 4 L X 2 1 8 W X 1 7 8 D such as RACO 660 or equivilent Box not included Black Blue The ATC consists of a momentary push button switch a key switch to enable disable the push button and an LED Turning the keyswitch to Test will enable the push button switch...

Page 5: ... contacts The connection to the waterflow zone of the fire panel involves 3 terminals on theVSR AT C and NO Connect the two wires fromthewaterflowzoneofthefirepaneltotheCandNOterminals with the End of Line Resistor of the fire panel being connected across the C and other terminal as shown on the drawing The NO and resistor terminal are internally connected by a normally energized relay Aloss of po...

Page 6: ... The NO and End of Line Resistor terminals are connected in ternally by a normally energized relay A loss of power or failed AutoTest causes the relay to drop out and initiates a trouble at the fire panel The only way to clear the trouble on the fire panel is to conduct a successful AutoTest using the ATC test switch or other test method Conducting an actual waterflow test will put the panel in al...

Reviews: