PSN-1000 POWER EXPANDER-5403599-REV C-04/17
13
5. Testing/Maintenance
The power supply board has one fuse on the board for the AC power over current protection.
The AC fuse is rated at 8A 250VAC Time-Lag and screened onto the main board as F1.
The batteries are to be replaced at least once every four years. The batteries are required to be UL recognized
batteries with a date of manufacture permanently marked on the battery. The battery is to be tested at least an
-
nually and if the battery is showing signs of failure, it is to be replaced.
The battery is to remain in the cabinet with nothing on or around the batteries. Only properly sized sealed lead
acid batteries are to be used with the control panel. Use of another battery or not providing the proper clearance
may result in a fire or an explosions.
The PSN-1000 is required to be installed in accordance with local and state building codes and NFPA 72 (Na
-
tional Fire Alarm Code).
The PSN-1000 and related system is required to be inspected and tested in accordance with NFPA 72.
6. Compatibilities
NAC Appliances
Please refer to Potter document 5403592-C NAC Compatibility Document
Releasing Circuit Devices
(All 24 VDC Devices, only one device per circuit)
Nohmi - Koatsu R85M14, R85M10-N
Skinner – 73218BN4UNLVNOC111C2
Skinner – 73212BN4TNLVN0C322C2
Victaulic – 753-E Series
Viking – 11591, 11601, 11602, 13843 and 13844.
Fireaway - Stat-X Models 30E, 60E, 100E, 250E, 500E, 1000E, and 2500E
Aero-K Models G30, G60, G100, G250, G500, G1000, G1500 and G2500
(Maximum of 10 per circuit)
Note: A Fireaway transient protection device (Part # 3005014) must be installed with each releasing
device