background image

MFG. #5400933 - REV E

09/12

PRINTED IN USA

 PAGE 3 OF 3

PS120 SERIES

SUPERVISORY PRESSURE SWITCH

DWG# 928-4

Break out thin section of divider to provide path for wires 

when wiring both switches from one conduit entrance.

One Conduit Wiring

Fig. 6

Fig. 8

DWG#928-5

Fig. 9

Removing Knockouts

C

C

C

1

2

C

1

2

LOW PRESSURE SWITCH

HIGH PRESSURE SWITCH

DWG# 930-3

Changing Pressure

Low Pressure Signal Connection

EOLR

TO FIRE ALARM PANEL

DWG# 928-1

EOLR

TO FIRE ALARM PANEL

DWG# 928-2

High Pressure Signal Connection

Fig. 5

Fig. 7

(With normal system pressure)

Engineer/Architect Specifications Pressure Type Waterflow Switch 

Pressure type supervisory switches; shall be a Model PS120 as 

manufactured by Potter Electric Signal Company, St. Louis, MO., and shall 

be installed on the fire sprinkler system as shown and or specified herein.

Switches shall be provided with a ½" NPT male pressure connection to be 

connected into the air supply line on the system side of any shut-off valve.

A Model BVL bleeder valve as supplied by Potter Electric Signal Company  

of St. Louis, MO., or equivalent shall be connected in line with the PS120 to 

provide a means of testing the operation of the supervisory switch. (See Fig. 3)
The switch unit shall contain SPDT (Form C) switch(es).  One switch shall 

be set to operate at a pressure decrease of 10 PSI (0,7 BAR)  from normal.  

If two switches are provided, the second switch shall be set to operate at a 

pressure increase of 10 PSI (0,7 BAR) from normal.
Switch contact shall be rated at 10.1 Amps at 125/250VAC and 2.0 Amps 

at 30VDC.  The units shall have a maximum pressure rating of 300 PSI 

(20,68 BAR) and shall be adjustable from 25 to 175 PSI (1,7 to 12,1 BAR).

• Installation must be performed by qualified personnel and in accordance with all national and   

   local codes and ordinances.

• Shock hazard. Disconnect power source before servicing. Serious injury or death could result.

• Read all instructions carefully and understand them before starting installation. Save   

   instructions for future use. Failure to read and understand instructions could result in improper  

   operation of device resulting in serious injury or death.

• Risk of explosion. Not for use is hazardous locations. Serious injury or death could result.

• Do not tighten by grasping the switch enclosure. Use wrenching flats on the 

   bushing only. Failure to install properly could damage the switch and cause 

   improper operation resulting in damage to equipment and property. 

 

• To seal threads, apply Teflon tape to male threads only.  Using joint compounds 

   or cement can obstruct the pressure port inlet and result in improper device 

   operation and damage to equipment.

• Do not over tighten the device, standard piping practices apply.

• Do not apply any lubricant to any component of the pressure switch. 

Terminal #1: Closed under 

normal system pressure.

Terminal #2: Open under 

normal system pressure, 

closes on pressure drop. Use 

for low pressure signal.

Terminal #1: Open under 

normal system pressure, closes 

on pressure increase. Use for 

high pressure signal.

Terminal #2: Closed under 

normal system pressure.

Reviews: