Appendix C: Module Specifi cations And Features
PFC-5002 Fire Alarm Control Panel
General
Two supervised Class B (Style B) or one Class A (Style D)
Initiating circuits; con
fi
gurable (normal or veri
fi
ed, and for
Class B there may be one water
fl
ow and one supervisory).
[Compatibility ID “A”]
Two Class A/B (Style Y/Z) NAC circuits; con
fi
gurable as
strobes or audibles.
Power limited: 24 VDC un
fi
ltered
1.7 A per circuit (2.0 a total)
Initiating circuit disconnect switch.
Optional UDACT or city tie adder module.
Optional ARM-4 / ARM-8 Relay Module.
Resettable four-wire smoke supply.
Power Limited: 28VDC, 100mA max, 1.5Vp-p ripple
Aux power supply.
Power limited: 24VDC, 300mA max, special application for
RTI or remote annunciators.
1 RTI Interface for connection to an RTI Remote Trouble
Indicator.
Auxiliary relays (resistive loads):
Common Alarm:
Form C, 1Amp, 28VDC
Common Trouble:
Form C, 1Amp, 28VDC
DIP switch con
fi
gurable.
Walktest function.
Electrical ratings
AC Line Voltage: 120V 0.74A 60Hz / 240V 0.34A 50/60Hz
Two amps (inline fuse on transformer primary)
Power supply ratings: 2.4 amps. max. (secondary)
For NAC circuits: 24VDC un
fi
ltered 2.0 amps. max.
Battery: 24VDC, gel-cell/sealed lead-acid
Charging capability: 4 to 24 AHr batteries
(cabinet will hold up to 8AH)
Current consumption:
standby
: 110 mA
/ alarm:
220 mA
PFC-5004E/PFC-5008 Fire Alarm Control Panel
General
Four supervised Style B (Class B) or 2 Style D (Class A)
initiating circuits; con
fi
gurable. [Compatibility ID “A”]
Power limited:26VDC, 3 mA standby, 1.5Vp-p ripple, 50 mA
max. (alarm)
Two Class A/B (Style Y/ Z) NAC circuits; con
fi
gurable as
strobes or audibles.
Power limited:24 VDC un
fi
ltered
1.7 A per circuit (5A total)
One ZA-42 Zone Adder Module may be added.
Initiating circuit disconnect switches.
Optional DACT or city tie adder module.
Optional ARM-4 / ARM-8 Relay Module.
Resettable four-wire smoke supply.
Power limited: 28VDC, 100mA max, 1.5Vp-p ripple
Aux power supply.
Power limited: 24VDC, 300mA max, special application
for RTI or Remote Annunciators
1 RS-485 connection for up to 3 RA8F Remote Annunciators.
1 RTI interface for connection to an RTI Remote Trouble Indicator.
Auxiliary relays (resistive loads):
Common Alarm:
Form C, 1Amp, 28VDC
Common Trouble:
Form C, 1Amp, 28VDC
Common Supervisory:
Form C, 1Amp, 28VDC
DIP switch con
fi
gurable.
Walktest function.
Electrical ratings:
AC Line Voltage:120V 1.65A 60Hz / 240V 0.64A 50/60Hz
Power supply ratings: 6 amps max. (secondary)
For NAC circuits: 24VDC un
fi
ltered, 5 amps max.
Battery: 24VDC, Gel-Cell/Sealed Lead-Acid
Charging capability: 4 to 24 AH batteries
(cabinet will hold up to 12AH)
Current consumption: standby: 110 mA / alarm: 220 mA
PFC-5004 Fire Alarm Control Panel
Same as PFC-5002, except ...
Only has four supervised Class B (Style B) or two Class A (Style
D) initiating circuits; con
fi
gurable (normal or veri
fi
ed).
[Compatibility ID “A”]
Zone 3 con
fi
gurable as Water
fl
ow
Zone 4 con
fi
gurable as Supervisory