PFC-5000 Series

4 or 8 Zone

Fire Alarm 

Control Panel

Installation, Operation, and 

Instruction Manual

(All speci

fi

 cations subject to revision.)

PFC-5004E

Summary of Contents for PFC-5000 Series

Page 1: ...GNAL COMPANY LLC St Louis MO 866 956 1211 314 595 6900 FAX 314 595 6999 www pottersignal com PFC 5000 Series 4 or 8 Zone Fire Alarm Control Panel Installation Operation and Instruction Manual All spec...

Page 2: ...g Considerations 12 Figure 11 A Main Fire Alarm Module Terminal Connections 13 Figure 11 B Main Fire Alarm Module Terminal Connections cont d 14 Figure 12 ZA 42 Zone Adder Module Terminal Connections...

Page 3: ...Relay Module ARM 4 or ARM 8 Terminal Connections 16 UDACT DACT UDACT 9100 Terminal Connections 17 Polarity Reversal and City Tie Module Model PR 5100 Terminal Connections 18 Power Supply Connections 1...

Page 4: ...Appendix B Remote Annunciators 36 Appendix C Module Specifications And Features 37 Appendix D Power Supply Battery Calculations 39 WARRANTY INFORMATION 40...

Page 5: ...004 or PFC 5004E Initiating Circuit 3 may be a Waterflow Zone as may Initiating Circuit 7 if a ZA 42 is installed and initiating circuit 4 may be a latched or non latched supervisory zone as may initi...

Page 6: ...are configured by default as Class B Style B They may be globally all or none configured as ClassA Style D as described in System Configuration on page 28 This operation uses odd and even pairs of two...

Page 7: ...ouble Indicator Resettable Four Wire Smoke Detector Power Supply May have two of UDACT 9100 or PR 5100 ARM 4 orARM 8 installed Can be used with BT 40 4AHr BT 80 8 AHr BT 120 120AHr BT 180 18AHr or BA...

Page 8: ...008 or PFC 5004E Adds four configurable Form C Relays rated 1A 28 VDC CircuitAdder Modules Model Description PR 5100 Polarity Reversal and City Tie Module UDACT 9100 Digital Communicator Model Descrip...

Page 9: ...ACKBOX DOOR 16 5 13 4 3 5 8 1 1 2 10 7 32 HOLE 12 4 3 8 7 8 15 8 1 8 1 14 1 8 3 3 3 1 4 1 6 x 5 16 SCREW KNOCKOUT 8 7 18 1 1 5 8 FINISH PAINTED MATERIAL 18GA 0 048 THICK COLD ROLLED STEEL Note Use Sec...

Page 10: ...OR BACKBOX SIDE VIEW SURFACE DOOR 4 5 1 BACKBOX SIDE VIEW FLUSH BACKBOX DOOR 16 5 WALL WALL 7 8 15 16 5 16 14 3 11 1 2 14 1 5 4 3 1 2 1 1 7 8 14 1 8 1 7 8 KNOCKOUT 12 2 1 8 3 1 2 8 3 4 2 6 x 5 16 SCRE...

Page 11: ...lid Earth Ground from building system ground or cold water pipe to the Chassis Earth Ground Mounting Lug and to connect the Earth Ground Wire Lugs from the Main Chassis to the ground screw on the back...

Page 12: ...5008 Module Mounting Locations P8 P7 DISPLAY PLATE ZONE ADDER MODULE ZA 42 MAIN FIRE ALARM MODULE P1 P6 MODEL PR 5100 POLARITY REVERSAL AND CITY TIE MODULE MODEL UDACT 9100 Note 1 Relay module may be...

Page 13: ...r on JW6 if a UDACT 9100 Digital Communicator is installed The digital communicator is plugged into P8 City Tie Remove the jumper on JW6 if a PR 5100 City Tie is installed The City Tie is plugged into...

Page 14: ...V ALM JW 8A SUPV JW7 8 Relay Modules ModelsARM 4 orARM 8 Figure 7 ARM 4 orARM 8 RelayAdder Module Zone Operated P1 Connect to P1 on the main fire alarm board By the factory setting the four or eight r...

Page 15: ...LEDs are illuminated amber reverse the wiring then wait 30 seconds for the LED to clear Please see the UDACT 9100 Manual LT 888POT for more information Polarity Reversal and City Tie Module Model PR 5...

Page 16: ...nection to the boards or runs to conduit The Figure below shows the required wiring techniques Figure 10 General Field Wiring Considerations USE AT LEAST 3 WIRE TIES AS SUPPLIED THROUGH HOLES ON DEADF...

Page 17: ...B WIRING ARE SHOWN BUT ONL Y ONE CLASS OF WIRING MAY BE USED IN ANY INSTALLATION SUPERVISED NAC 1 POWER LIMITED REGUL ATED 24FWR BELL HORN OR STROBE Legend See Appendix A forcompatible devices 3 9K 1...

Page 18: ...Y MIRCOM PULL STATION S RS 485 1 2 OR 3 REMOTE ANNUNCIATORS SEE APPLICABLE OPERATION INS T ALLATION MANUAL NOT USED WITH RTI CLASS B STYLE 4 WIRING 24VDC POWER POWER LIMITED 4 WIRE SUPPL Y INI1 INI1 I...

Page 19: ...IMITED SUPERVISED INITIATING CIRCUIT 7 SHOWN AS ALARM ZONE POWER LIMITED SUPERVISED INITIATING CIRCUIT 3 POWER LIMITED NAC 4 Z NAC 4 Z NAC 4 Y Z SUPERVISED NAC 4 POWER LIMITED REGULATED 24 FWR NAC 3 Z...

Page 20: ...CTS 28 VDC 1 AMP RESISTIVE LOAD RELAY CONTACTS 28 VDC 1 AMP RESISTIVE LOAD RELAY CONTACTS 28 VDC 1 AMP RESISTIVE LOAD RELAY CONTACTS 28 VDC 1 AMP RESISTIVE LOAD RELAY CONTACTS 28 VDC 1 AMP RESISTIVE L...

Page 21: ...Connector terminals as shown in Figure 14 below The UDACT 9100 terminals are located on the top left hand corner of the board If using a cellular or wireless service use the Line interface connection...

Page 22: ...Figure 15 PR 5100 Polarity Reversal and City Tie Module Terminal Connections When wiring devices please keep in mind the following Plug PR 5100 ribbon cable P1 into the main fire alarm module All cir...

Page 23: ...40V 50 Hz 1 0A Do not exceed power supply ratings To prevent sparking connect batteries after the systems mainA C power is turned on Figure 16 Power Supply Connections P2 MAIN FIRE ALARM MODULE GREEN...

Page 24: ...to Last Device ELR Max Loop Resistance Amperes ft m ft m ft m ft m Ohms 0 06 2350 716 3750 1143 6000 1829 8500 2591 30 0 12 1180 360 1850 567 3000 915 4250 1296 15 0 30 470 143 150 229 1200 366 1900 5...

Page 25: ...in the System Configuration section on page 28 Troubleshooting Message Description Circuit Trouble Normally when a circuit trouble occurs its designated trouble indicator will be illuminated as well...

Page 26: ...f the following Fire alarm steady Supervisory alarm fast flash rate of 120 beeps per minute Trouble slow flash rate of 20 beeps per minute If the buzzer turns on in response to a non latching trouble...

Page 27: ...sory relays and anyARM 4 ARM 8 relays are not activated The trouble relay is activated If installed DACT or polarity reversal and city tie modules are also inactive causing a trouble condition Signal...

Page 28: ...Activating theAuxiliary Disconnect momentary switch activates the auxiliary disconnect function Activating the switch again de activates the function When auxiliary disconnect is active common alarm...

Page 29: ...is not active Signals and strobes are activated SubsequentAlarms when the panel is already in alarm cause the following The buzzer sounds steadily If signals have been silenced as a result of the sig...

Page 30: ...ial activation will cause that circuit to alarm immediately This is a fail safe operation that handles any fire induced wiring faults Water FlowAlarm An alarm for water flow sensors These alarms are i...

Page 31: ...ly While sounding these follow the pattern appropriate for the condition the configured evacuation code default is temporal code during single stage alarm or two stage general alarm or the alert code...

Page 32: ...P6 P6 SW13 SW13 A B JW2 JW2 P3 P3 A B BATT BATT P4 P4 P5 P5 P2 P2 BATT BATT GND GND XMFR XMFR XMFR XMFR JW1 JW1 P7 P7 P8 P8 JW4 JW4 JW3 JW3 JW6 JW6 SW11 SW11 SW9 SW9 P1 P1 SUPV SUPVRLY LY C O M C O M...

Page 33: ...effect on Supv Switch 11 6 Alarm Supervisory Switch 11 7 Non Latching Supervisory No effect onAlarm Latching Supervisory No effect onAlarm Application ofAC Power Fail Delay Switch 11 8 NoAC Power Fai...

Page 34: ...e selection of ClassA B Style Z Y NAC circuits is only a matter of how they are wired See connection information on page 13 If ClassA Style D initiating circuits are selected JW1 and JW2 jumpers must...

Page 35: ...If this is not done then a Switch Tamper Trouble will occur Perform a hard reset by pressing SW0 push button switch on back of main panel pcb Do not use retard operation with any external retarding de...

Page 36: ...walk tested and so on For example if Initiating Circuit 3 is first activated the indication circuits will sound for three bursts Any subsequent activations of Initiating Circuit 3 will sound for one b...

Page 37: ...DCD 190 NS6 220 6266C PSD 7130 70 201000 002 DCD 190 NS4 220 6269C PSD 7130 70 201000 003 DCD 190 HSC 220R 6270C PSD 7130 70 201000 005 SIJ 24 NS6 220 6269C 003 PSD 7128 70 201000 001 SIJ 24 NS4 220...

Page 38: ...040mA 2400TH A N A 0 12 mA SIJ 24 HSC 220R HD 3 HB 3 0 040mA 2400AT A N A 0 12 mA SLR 24 NS6 220 HD 3 HB 72 0 045mA 2400AIT A N A 0 12 mA SLR 24 NS4 220 HD 3 HB 3 0 045mA 2451 B401B A A 0 12 mA SLR 2...

Page 39: ...AS 24100C FW AH 24 R AH 24 WP R NS 2415W FR NS 241575W FR NS 2430W FR NS 2475W FR NS 24110W FR NS4 2415W FR NS4 241575W FR NS4 2430W FR NS4 2475W FR NS4 24110W FR RS 2415W FR RSS 241575W FR RSS 2415W...

Page 40: ...mounts in an electrical box It provides annunciation for the PFC 5004 PFC 5008 or PFC 5004E s full complement of 8 Initiating circuits For more detailed information see Potter Document 8900103 PFC 50...

Page 41: ...el General Four supervised Style B Class B or 2 Style D ClassA initiating circuits configurable Compatibility ID A Power limited 26VDC 3 mAstandby 1 5Vp p ripple 50 mA max alarm Two ClassA B Style Y Z...

Page 42: ...PR 5100 Supervised city tie not power limited 24VDC unfiltered 210 mAmax Trip coil 14 ohms Polarity reversal power limited 24VDC open 12VDC 3 5 mA 8 mAmax shorted Current consumption standby 35 mA al...

Page 43: ...035 0 090 RTI 1 Remote Trouble Indicator 0 035 0 035 Two Wire Smoke Detectors 0 0001 0 090 0 090 Four Wire Smoke Detectors X Signal Load bells horns strobes and etc Auxiliary Power Supply for RemoteA...

Page 44: ...ion or repair by unauthorized persons or if for any other reason POTTER determines that said product is not operating properly as a result of causes other than defective manufacture labeling or packag...