background image

 INSTALLATION MANUAL: PAD200-DUCT ANALOG ADDRESSABLE DUCT DETECTOR

Document 5406428-A  02/21

Potter Electric Signal Company, LLC           •           St. Louis, MO             •           Phone: (800) 325-3936               •            www.pottersignal.com

 

PAGE 3 OF 4

5.  Mechanical Installation Instructions

LOCATION PREREQUISITES

:

 

This guideline contains general information on the PAD200-DUCT duct smoke detector installation, 

but does not preclude the NFPA and/or ICC documents listed. Potter Electric Signal Company assumes no responsibility for 

improperly installed duct detectors. To determine the correct installation position for a PAD200-DUCT duct smoke detector, the 

following factors must be considered.

A.  A uniform non-turbulent (laminar) airflow between 100 ft/min. to 4,000 ft/min. must be present in the HVAC duct. To determine 

duct velocities, examine the engineering specifications that define the expected velocities or use an Alnor model 6000AP 

velocity meter (or equivalent).

B.  To minimize the impact of air turbulence and stratification on performance, a duct smoke detector should be located as far 

as possible downstream from any obstruction (i.e. deflector plates, elbows, dampers, etc.). In all situations, confirmation of 

velocity and pressure differential within specifications is required.
The pressure differential between the input sampling high pressure) tube and exhaust (low pressure) tube for the PAD200-

DUCT duct smoke detector should be greater than 0.01 inches of water and less than 1.2 inches of water.

C.  Identify a code compliant location (supply or return side, or both) for the installation of the duct unit that will permit easy access 

for viewing and serviceability.

D.  When installing on the return side, install duct units prior to the air being exhausted from the building or diluted with outside 

“fresh” air.

E.  When installing duct smoke units downstream of filters, fires occurring in the filters will be detected, but if the filters become 

blocked, insufficient air flow through the duct unit will prevent the correct operation of the duct detector. Duct units installed in 

the supply air side may monitor upstream equipment and/or filters.

F.  Where possible, install duct detectors upstream of air humidifiers and downstream of dehumidifiers.

G.  To prevent false alarms, the duct detector should not be mounted in areas of extreme high or low temperatures, in areas 

where high humidity exists, or in areas where the duct may contain gases or excessive dust.

SAMPLING TUBE ASSEMBLY: 

The PAD200-DUCT duct smoke detectors employ a specially notched sampling tube, which may 

be ordered separately in one of four (4) standard lengths.

STN-1.0   For duct widths of 6” TO 1.0’

STN-2.5   For duct widths of 1.0’ TO 3.0’

STN-5.0   For duct widths of 3.0’ TO 5.0’

STN-10.0   For duct widths of 5.0’ TO 10.0’

Standard sampling tubes are steel tubes with air intake holes located the entire length of the tube. These tubes must be cut to 

length and should span the entire width of the duct. Sampling tubes over 3.0’ must be supported on the opposite side of the duct. 

To ensure the correct operation of the sensing tube, the red end cap (red stopper in installation kit) must be inserted in the end 

of the air intake sampling tube. For custom duct widths, always use the next longest standard size and cut down to the exact 

requirement.

“NO-TOOLS” TUBE INSTALLATION: 

The PAD200-DUCT duct smoke detector provides a unique, patented mechanism for 

installation and/or removal of the sampling and exhaust tubes from either the front or rear of the detector housing. Once the airflow 

direction has been determined, insert the inlet and exhaust tubes into the duct smoke detector. If the cover is in place, the tubes 

may be inserted into the back of the detector via the key-slots provided. Simply push the tube into place against the spring loaded 

retainer, and turn into the correct position, allowing the key to “lock” the tube in the desired orientation. For front side installation, 

simply rotate the tube retainer until the tube may be inserted and oriented properly. Once the tube is installed, rotate the retainer 

back into place to lock down the tube. Ensure air intake sampling tube is positioned so that the inlet holes are directly facing the 

airflow.

Figure 4. Example of the PAD200-DUCT Duct Detector Placement

INLET TUBE
HOLES FACE
AIR FLOW

DUCT WIDTH

AIR FLOW DIRECTION

INSERT RED STOPPER 
THIS END OF INLET TUBE

EXHAUST TUBE INSTALLED 
DOWNSTREAM OF AIRFLOW
DO NOT INSERT RED STOPPER

NOTE: Mountings shown 
are typical.   Detectors can 
be installed side, bottom 
or top of duct as long as 
proper tube operation and 
flow/pressure performance 
is maintained

Tube Support Hole only for Ducts Greater than 3 Feet Wide

Summary of Contents for PAD200-DUCT

Page 1: ...e ordered Sampling tubes are supplied in three standard lengths 2 5 ft 5 ft and 10 ft and cut to size to fit the duct Mounting the duct smoke unit is accomplished by the use of a template and 2 sheet metal screws which are provided Mounting can be achieved without the removal of the clear cover which is secured by 4 capture screws 2 Setting the Address All PAD protocol detectors and modules requir...

Page 2: ...ir Velocity 100 to 4000 ft min Ambient Temperature 32 to 120 F 0 to 49 C Humidity 10 to 85 Relative humidity non condensing Housing Material Plastic backbox clear plastic cover Finish Gray backbox with clear cover Dimensions 13 1 2 L x 4 1 2 W x 2 1 4 D Maximum Net Weight 2 lbs Sampling Tubes 2 5 ft 5 ft or 10 ft Sampling Tube Part Numbers 2 5 1000274 5 1000275 10 1000276 4 Wiring Diagram The wiri...

Page 3: ...e alarms the duct detector should not be mounted in areas of extreme high or low temperatures in areas where high humidity exists or in areas where the duct may contain gases or excessive dust SAMPLING TUBE ASSEMBLY The PAD200 DUCT duct smoke detectors employ a specially notched sampling tube which may be ordered separately in one of four 4 standard lengths STN 1 0 For duct widths of 6 TO 1 0 STN ...

Page 4: ...te Be sure to dis engage all alarm signal services releasing devices and extinguishing systems prior to performing the following test except automatic testing by the FACP Be sure to re engage these systems when all testing is complete 8 Walk Test The FACP must be placed into Walk Test Mode and follow the steps below Use the appropriate steps outlined below for the detector that is to be tested Not...

Reviews: