Battery Location 

22.

 

Mount two 12V batteries in lower part of enclosure, see below for correct orientation.   

23.

 

Note position of ‘H’ box brackets for each battery option.   

24.

 

Ensure all battery terminals are sufficiently insulated to prevent accidental shorting to each other or the 

enclosure metalwork. 

 

Warning: Always use two 12V batteries connected in series.  This product will not work with one 12V battery

.

 

 

 

 
 

 

 
 

 

 

 
 

 

 
 

 

 

                                                          

 

 

 
 

 

 

 

 

 

 
 

 

 
 

 

 
 

 

Compatible Batteries 

Battery Capacity (2x 12V) 

Type (closed) VRLA.: 

  PowerSonic                             model 
  Yuasa                                        model 
  Interlogix                                 model 

       Europa                                     model

 

7 Ah 

 

PS-1270 

NP7-12 

BS127N 

EB12-7.2 

12 Ah 

 

PS-12120 

NP12-12 

BS130N 

EB12-12 

17/18 Ah 

 

PS-12180S 

NP17-12I 

BS131N 

EB12-18 

24 Ah 

 

PS-12260S 

NP24-12I 

BS129N 

EB12-26 

38 Ah 

 

PS-12380 
NP38-12I 

BS132N 

EB12-44 

 

25.

 

Where a dual box solution (PSE and CIE in separate enclosures) is used all cabling between the two 

boxes should be routed to use separate case entry/exit holes from other cabling using suitable cable 
glands to protect the cables

 

26.

 

Connect the two 12 V standby batteries in series using the single link cable provided. Connect the 

negative

 of one battery to the 

positive

 of the 

other

 battery.  

2402ST in C box with 7Ah 

batteries 

2402ST in E box with 17Ah 

batteries 

2402ST in K box with 12Ah 

batteries 

 

2402ST in H box with 24Ah batteries 

(battery omitted for clarity) 

 

2402ST in H box with 38Ah batteries  

Fit retaining 

brackets 

Fit spacers  

Summary of Contents for Elmdene 2402ST Series

Page 1: ...5 Installation cont Battery Charger settings 6 Installation cont Battery installation Battery compatibility 7 Installation cont Battery installation Final commissioning 8 Operating Instructions and Maintenance 9 Trouble shooting 10 Developer Section DUAL PATH RS485 communication link 11 Disposal and Product Compliance Elmdene International Ltd Tel 44 0 23 9269 6638 3 Keel Close Interchange Park Fa...

Page 2: ...n From In to In 15 for an output voltage 50 Un Fuse Load OP1 and OP2 F2 0 A IEC 60127 2 type Battery Charging Constant current bulk charging to 80 capacity within 24 hours Float charging to 100 within 48 hours with monitored ECO charging Battery Voltage Low battery threshold voltage Deep discharge protection 23 2 V measured at the battery 21 6 V minimum measured at PSU output Quiescent current At ...

Page 3: ...s used for other applications it should be installed according to all relevant safety regulations applicable to that application Cable Sizing 4 Mains input cable must be to the applicable standard with a 5A or greater current capacity i e 0 75 mm2 nominal conductor area having a minimum operating voltage of 300 500V ac 5 The low voltage output cable must be sized to carry the rated load current to...

Page 4: ...onnect the mains power using the disconnect device Connecting the Remote Signalling 14 Connect the EPS and GEN PSU Fault outputs to the appropriate inputs of CIE EPS Fault GEN Fault Condition Possible Cause Action COM TO N C CLOSED COM TO N C CLOSED Normal operation Mains present Battery healthy None COM TO N C OPEN COM TO N C CLOSED Standby Mode Mains lost 8 seconds Battery driving load Investiga...

Page 5: ...tery Charger Setting 21 Set the correct charger mode by fitting the jumper to the appropriate charger mode header Use the table below to select the appropriate charger mode Battery mode selected Mode 1 DEFAULT Mode 2 Mode 3 Battery Capacity 2x 12V 7 Ah 12 Ah 17 18 Ah 24 Ah 38 Ah EN54 4 Continuous Output Current No charging Imax B With Charging Imax A 2 5 A 2 0 A 2 5 A b 1 75 A 2 5 A c 1 0 A Consta...

Page 6: ...Ah PS 1270 NP7 12 BS127N EB12 7 2 12 Ah PS 12120 NP12 12 BS130N EB12 12 17 18 Ah PS 12180S NP17 12I BS131N EB12 18 24 Ah PS 12260S NP24 12I BS129N EB12 26 38 Ah PS 12380 NP38 12I BS132N EB12 44 25 Where a dual box solution PSE and CIE in separate enclosures is used all cabling between the two boxes should be routed to use separate case entry exit holes from other cabling using suitable cable gland...

Page 7: ...ault Then wire the batteries to the terminals follow steps 27 28 Once the batteries are charging clear the thermistor fault by reconnecting the thermistor wire 30 Verify GEN Fault relay n c contact is closed com to n c terminals short circuit 31 Disconnect the mains power Verify that the green Mains LED 1 extinguishes and the Yellow Fault LED 3 starts to flash indicating that the PSE is running fr...

Page 8: ...a second click while the charger is tested Note If it is necessary to obtain confirmation of charging current between steps 28 and 29 an ammeter can be placed in series with the battery leads Continue to observe caution with all exposed conductors when inserting or removing the meter and when restoring normal battery wiring 40 Close cover and secure using fastening screws provided OPERATING INSTRU...

Page 9: ... YELLOW Fast Flash Battery in process of connecting Battery connecting No action Wait for battery connection to complete GREEN Flash x1 Normal operation Battery connected Battery in bulk charge No action Battery charging normally GREEN Normal operation Battery connected Battery healthy No action System healthy Battery in good state of charge YELLOW Battery fault Battery disconnected Low Battery Vo...

Page 10: ...rger Return to manufacturer RED Flash x5 Battery Temperature Probe Fault Battery temperature monitor disconnected or damaged PSU running in Safe Mode Check temperature sensor connections and condition of sensor Replace if suspect RED Flash x6 Dual Path Fault Fault in output connections to the load DUAL PATH mode active only Check all cables between PSU and load OP1 OP2 LEDs 5 or 6 Condition Possib...

Page 11: ... OF LIFE This product falls within the scope of EU Directives 2012 19 EU Waste Electrical and Electronic Equipment WEEE and 2013 56 EU Battery At the end of life the product must be separated from the domestic waste stream and disposed via an appropriate approved WEEE disposal route in accordance with all national and local regulations Before disposal of the product any batteries must be removed a...

Page 12: ...005 Environmental Class I Equipment Class A Suitable for all systems VdS 2541 1996 12 G220015 Environmental Class III Certification Bodies AFNOR CNPP VdS Declaration of Performance DOP2018 022 DOP2018 023 DOP2018 024 DOP2018 025 0333 Elmdene International Ltd 3 Keel Close Portsmouth PO35QD 19 0333 CPR 075603 EN54 4 1997 A1 A2 EN12101 10 2005 Power Supplies intended for use in fire detection and fi...

Reviews: