Figure 4 – Terminal layout and mode selection 

 

 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
Dual-Path power transmission monitoring feature 

41.

 

The 2402ST PSU has an optional mode designed to 

work with systems that require dual-power 
transmission paths.  When enabled, the PSU compares 

the outputs and reports a load imbalance of more than 

10% as an OUTPUT FAULT (LED 4 x6 Flashes) and is 
enabled by removing the header marked 

OP1 

 OP2

 

 

This mode meets the requirements of EN54-13 Section 

5.3.3.1 S

FAULT 

and Section 5.3.4.2 P

FAULT 

warning 

conditions, for loads above 200mA. 

It is still necessary for the connected equipment to be 

designed to accept two separate power inputs, such 
that a short to ground of either power transmission 

path, will not inhibit the equipment performance. 

 

 

PSU Addressable Data link communication protocol 

 

42.

 

The 2402ST PSU has an addressable RS485 communication port, that can be enabled to provide the 
internal PSU data, and includes; Mains Voltage; Output1 Voltage/Current; Output2 Voltage/Current; 

Battery Voltage; Charger Current; Charger setting; GEN Fault condition; EPS Fault condition; Diagnostics 

fault status (condition 1-6), Battery temperature, Charger status, unit address 

43.

 

To enable this feature and obtain the protocol guide, please contact Elmdene Technical Support  

 

 

D

ISPOSAL OF 

P

RODUCT AT 

E

ND OF 

L

IFE

 

 

 

This product falls within the scope of EU Directives 2012/19/EU Waste Electrical and Electronic Equipment (WEEE) and 2013/56/EU (Battery). At 
the end of life, the product must be separated from the domestic waste stream and disposed via an appropriate approved WEEE disposal route 
in accordance with all national and local regulations. 
Before disposal of the product, any batteries must be removed, and disposed separately via an appropriate approved battery disposal route in 
accordance  with  all  national  and  local  regulations.  Package  used  batteries  safely  for  onward  transport  to  your  supplier,  collection  point  or 
disposal facility. 

Caution:  Risk of fire or explosion if bare battery wires are allowed to touch. 

 
See Specification for battery type information. The battery is marked with the crossed-out wheelie bin symbol, which may include lettering to 
indicate cadmium (Cd), lead (Pb), or mercury (Hg). 

For more information see: 

www.recyclethis.info

 

 

The packaging supplied with this product may be recycled.   Please dispose of packaging accordingly. 

Mains 

Input 

Load 

Outputs 

Battery 

Connection 

 

GEN & EPS 

Relay Outputs 

 

‘No battery’ 

Select 

 

Unit Add 

Select 

RS485 

Link 

Temp Probe 

Inputs 

OP2 

Fuse 

PTC Battery 

Fuse 

OP1 ≠ OP2 

Select 

LED Status 

Indicators 

Charger 

Setting 

OP1 

Fuse 

Mains  

Fuse 

OP1≠OP2 

DUAL-PATH ACTIVE 

DUAL-PATH MODE FAULT SIGNALLING

-

PSU LOAD OUTPUT

1    &    2

+

DU AL PATH LOAD I NPUT

-

+

-

+

FA ULT SIGNALLED WHEN 

M O RE T HAN 1 0% 
I M BALANCE BETWEEN 

P A THS 

RE F: E N 54-13 5 .3 .4.1 S

FAULT 

& 5 .3 .4 .2  P

FAULT 

V ALUES

+

-

* E quipment must be have 2 s eparate power inputs c apable of 

withs tanding a s hort to ground on one path

 

Summary of Contents for Elmdene 2402ST Series

Page 1: ...5 Installation cont Battery Charger settings 6 Installation cont Battery installation Battery compatibility 7 Installation cont Battery installation Final commissioning 8 Operating Instructions and Maintenance 9 Trouble shooting 10 Developer Section DUAL PATH RS485 communication link 11 Disposal and Product Compliance Elmdene International Ltd Tel 44 0 23 9269 6638 3 Keel Close Interchange Park Fa...

Page 2: ...n From In to In 15 for an output voltage 50 Un Fuse Load OP1 and OP2 F2 0 A IEC 60127 2 type Battery Charging Constant current bulk charging to 80 capacity within 24 hours Float charging to 100 within 48 hours with monitored ECO charging Battery Voltage Low battery threshold voltage Deep discharge protection 23 2 V measured at the battery 21 6 V minimum measured at PSU output Quiescent current At ...

Page 3: ...s used for other applications it should be installed according to all relevant safety regulations applicable to that application Cable Sizing 4 Mains input cable must be to the applicable standard with a 5A or greater current capacity i e 0 75 mm2 nominal conductor area having a minimum operating voltage of 300 500V ac 5 The low voltage output cable must be sized to carry the rated load current to...

Page 4: ...onnect the mains power using the disconnect device Connecting the Remote Signalling 14 Connect the EPS and GEN PSU Fault outputs to the appropriate inputs of CIE EPS Fault GEN Fault Condition Possible Cause Action COM TO N C CLOSED COM TO N C CLOSED Normal operation Mains present Battery healthy None COM TO N C OPEN COM TO N C CLOSED Standby Mode Mains lost 8 seconds Battery driving load Investiga...

Page 5: ...tery Charger Setting 21 Set the correct charger mode by fitting the jumper to the appropriate charger mode header Use the table below to select the appropriate charger mode Battery mode selected Mode 1 DEFAULT Mode 2 Mode 3 Battery Capacity 2x 12V 7 Ah 12 Ah 17 18 Ah 24 Ah 38 Ah EN54 4 Continuous Output Current No charging Imax B With Charging Imax A 2 5 A 2 0 A 2 5 A b 1 75 A 2 5 A c 1 0 A Consta...

Page 6: ...Ah PS 1270 NP7 12 BS127N EB12 7 2 12 Ah PS 12120 NP12 12 BS130N EB12 12 17 18 Ah PS 12180S NP17 12I BS131N EB12 18 24 Ah PS 12260S NP24 12I BS129N EB12 26 38 Ah PS 12380 NP38 12I BS132N EB12 44 25 Where a dual box solution PSE and CIE in separate enclosures is used all cabling between the two boxes should be routed to use separate case entry exit holes from other cabling using suitable cable gland...

Page 7: ...ault Then wire the batteries to the terminals follow steps 27 28 Once the batteries are charging clear the thermistor fault by reconnecting the thermistor wire 30 Verify GEN Fault relay n c contact is closed com to n c terminals short circuit 31 Disconnect the mains power Verify that the green Mains LED 1 extinguishes and the Yellow Fault LED 3 starts to flash indicating that the PSE is running fr...

Page 8: ...a second click while the charger is tested Note If it is necessary to obtain confirmation of charging current between steps 28 and 29 an ammeter can be placed in series with the battery leads Continue to observe caution with all exposed conductors when inserting or removing the meter and when restoring normal battery wiring 40 Close cover and secure using fastening screws provided OPERATING INSTRU...

Page 9: ... YELLOW Fast Flash Battery in process of connecting Battery connecting No action Wait for battery connection to complete GREEN Flash x1 Normal operation Battery connected Battery in bulk charge No action Battery charging normally GREEN Normal operation Battery connected Battery healthy No action System healthy Battery in good state of charge YELLOW Battery fault Battery disconnected Low Battery Vo...

Page 10: ...rger Return to manufacturer RED Flash x5 Battery Temperature Probe Fault Battery temperature monitor disconnected or damaged PSU running in Safe Mode Check temperature sensor connections and condition of sensor Replace if suspect RED Flash x6 Dual Path Fault Fault in output connections to the load DUAL PATH mode active only Check all cables between PSU and load OP1 OP2 LEDs 5 or 6 Condition Possib...

Page 11: ... OF LIFE This product falls within the scope of EU Directives 2012 19 EU Waste Electrical and Electronic Equipment WEEE and 2013 56 EU Battery At the end of life the product must be separated from the domestic waste stream and disposed via an appropriate approved WEEE disposal route in accordance with all national and local regulations Before disposal of the product any batteries must be removed a...

Page 12: ...005 Environmental Class I Equipment Class A Suitable for all systems VdS 2541 1996 12 G220015 Environmental Class III Certification Bodies AFNOR CNPP VdS Declaration of Performance DOP2018 022 DOP2018 023 DOP2018 024 DOP2018 025 0333 Elmdene International Ltd 3 Keel Close Portsmouth PO35QD 19 0333 CPR 075603 EN54 4 1997 A1 A2 EN12101 10 2005 Power Supplies intended for use in fire detection and fi...

Reviews: