PULSERPLUS PRO™ HIGH RESISTANCE GROUNDING SYSTEM
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
4750 Olympic Blvd. • Erlanger, KY 41018 • USA
Phone: 800-537-6144 / 859-283-0778 • Fax: 859-283-2978
www.postglover.com
Serving the Electrical Industry Since 1892
PGR Document #HG111-06
© 2006 Post Glover Resistors, Inc.
PULSERPLUS PRO™ HIGH RESISTANCE GROUNDING SYSTEM
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
4750 Olympic Blvd. • Erlanger, KY 41018 • USA
Phone: 800-537-6144 / 859-283-0778 • Fax: 859-283-2978
www.postglover.com
Serving the Electrical Industry Since 1892
© 2006 Post Glover Resistors, Inc.
15
6.3 Configuration Mode
To Enter Configuration Mode
Press BOTH the RESET and DOWN ARROW buttons until the unit BEEPS, then release.
Adjusting Values in Configuration Mode
Numeric values can be adjusted by using the UP ARROW and DOWN ARROW buttons. The buttons have two
speeds. If either button is held in, the display will increment / decrement by single units for 5 counts, then it will
increment / decrement by ten units. Releasing the button will restore the single units counting.
Pressing the ENTER button will store the NEW value and go to the next setting.
Pressing the MODE button will go to the next setting WITHOUT changing the stored setting.
Pressing the PULSE button will go back to the previous screen WITHOUT changing the stored setting.
To Exit Configuration Mode
Pressing the RESET button will EXIT configuration mode.
After 60 seconds of inactivity, the unit will exit configuration mode and return to displaying fundamental and/or
harmonic measurements.
6.4 Measurement Enable
Using the UP ARROW and DOWN ARROW buttons, the Fundamental Voltage and Amperage, and the 3
rd
Harmonic Voltage and Amperage measurement displays can be enabled or disabled. Measurement displays
default to the ENABLED condition.
6.5 Current Transformer Ratio
Fnd Vlt Meas On
(Off/On)
Hrm Vlt Meas On
(Off/On)
Fnd Amp Meas On
(Off/On)
Hrm Amp Meas On
(Off/On)
CT Ratio XXX
Selection XX