5
IMPORTANT: Controllers may only allow configuring signed values. In order to set values in
the range 128… 255 the value sent in the application shall be the desired value minus 256.
For example: to set a parameter to 200
it may be needed to set a value of 200 minus 256 =
minus 56. In case of a two byte value the same logic applies: Values greater than 32768
may needed to be given as negative values too.
Siren triggering mode (Parameter Number 1, Size 1)
Sets the tamper triggering mode when removed from the holder
Value Description
0
The Siren triggers automatically when it's removed from the holder. Must be
turned off, using the button or from the controller (Default)
1
The Siren triggers automatically when it's removed from the holder and turns off,
when placed back on the holder
2
Siren doesn't trigger at all, when removed from the holder. Service Mode
Temperature adjustments (Parameter Number 2, Size 1)
Temperature correction. For positive value 10 = 1 °C, for negative value x = 256 - (T°C * 10).
Example, if need shift -2.6°C, value calculate: 256 - (2.6 * 10) = 230.
Value
Description
0
Disabled (Default)
1 – 127
In 0.1°C (Default 0)
128 – 255
-0.1°C
Send unsolicited temperature report (Parameter Number 3, Size 1)
Threshold temperature to send unsolicited report. 10 = 1°C
Value
Description
0 – 255
In 0.1°C (Default 10)
Send unsolicited temperature report after N wake up (Parameter Number 4, Size 2)
If the value is set, after N wake up number (measurement is every 4 minutes) the
temperature report will be sent. By default it's 15 = every 1 hour
Value
Description
0
Disabled
1 – 65535
Each N
th
wake up time (Default 15)
Switch mode: siren only, flash only, flash + siren (Parameter Number 5, Size 1)
Value
Description
0
Siren only
1
Flash only
2
Flash + Siren (Default)