42
EGW05-SWHPEG-20140724
TM
TM
Units in Pits
The top of the unit should be level with the top of the pit and side distances increased to “2W”. If the top of the units is
not level with the top of the pit, discharge cones or stacks must be used to raise discharge air to the top of the pit. This is
a minimum requirement.
Figure 4-6. Remote ACC Installation When Installing Units in Pits
Decorative Fences
Fences must have 50% free area, with 1 foot undercut, a “W” minimum clearance, and must not exceed the tops of the
unit. If these requirements are not met, the unit must be installed as indicated for “Units in Pits”.
Figure 4-7. Remote ACC Installation When Installing Units Near Decorative Fences
* W”=Total width of the condenser
”
MIN.
MIN.
AIR
FLOW
2W*
2W*
STACK
(BY OTHERS
IF SUPPLIED)
10’ MAX.
* W”=Total width of the condenser
”
MIN.
1”
MIN.
MIN.
AIR FLOW
W*
W*