Plumbing Diagrams
For systems with pumps of less than 2 HP (under 80 gpm ), no external bypass is required.
Connections are 2-inch unions. Plumb the heat pump
after
the filter and
before
any
chlorinators.
For systems with pumps of 2 HP or greater (over 80 gpm ), an external bypass is required.
Adjust the bypass valve to divert a minimum of 40 gpm through the heat pump. Connections
are 2-inch unions. Plumb the heat pump
after
the filter and
before
any chlorinators.
Filter
Water In
(from pool
or spa)
Water Out
(to pool
or spa)
Filter
Water In
(from pool
or spa)
Water Out
(to pool
or spa)