7. Replace feed tubing.
a) Cut 2x lengths of new feed tubing as required:
1 x for pump to injector connection.
1 x for pump to reservoir connection
b) Connect tubing from pump outlet to injector, and tighten lock nuts by hand only.
While tightening the injector lock nut, hold the injector body in place with a spanner to prevent
over-tightening the cell housing thread.
c) Connect tubing to pump inlet and tighten lock nut.
8.
Prepare the system for operation.
a) Check all pipe unions are tight.
b) Check both suction and return valves are open and positioned correctly.
c) Ensure the filtration mode is set to OFF, and reconnect filter pump power lead to the pump
outlet socket.
9.
Start the system, and check for leaks.
a) Change filtration mode to ON using the MODE button.
b) Ensure water is flowing normally, and pressure gauges reading normal.
c) Check plumbing, feed tubing and connectors for any signs of leaks
10.
Test pump operation with water, using the prime function
a) Place the inlet end of the acid feed tube in a bucket of fresh water.
b) On the chlorinator control panel, press and hold VIEW until the MAIN MENU appears.
c) Navigate to ASP TOOLS and press VIEW (ASP TOOLS menu appears)
d) Navigate to ACID/LCHL PRIME and press VIEW
e) Press VIEW to start the feed pump (60 second
count down timer begins)
f) Observe water being pumped along the feed tubes
11. Fit fume stop cap back onto reservoir. Ensure the
end of the feed tube can reach the bottom of the
drum and adjust length if required.