PW-VP50 CT Polarity Checker
6
The three ports will be connected with the CT primary current.
Buttons on the master machine:
Power:
Press the power button 3 seconds to switch on or switch off the master machine.
Phase output:
It is used to set the output phase of the current pulse. Phase A, B, C or
three-phase can output simultaneously.
Period
: It is used to set the pulse output period: 2 second, 3 second, 4 second and five
second for setting.
Max current:
It is used to set the max pulse current injected to the CT primary side. There
are four grades: 1A, 2A, 3A and 5A. The higher of the max current, the higher of the
induced current in CT secondary; If so, the power consumption will be higher and the
battery working time will be shorter. We suggest using the 5A option when the CT ratio is
higher than 4000/5; and using 1A or 2A or 3A option with CT ratio lower than 4000/5.
Single trigger:
It is used to send the single current pulse.
Cyclic trigger: By pressing it, the checker will output the current pulse with the setting
cycle.
Default:
The checker will working with the default mode setting: three-phase output, max
current 1A, period 3s and cyclic trigger.