PCT200 Series CT/PT Test System User Manual
58
In this case the FS is 5 on the CT nameplate, but the FS>4.016.
It means while making this kind of CT, the PCT can only test FS at 4.016 times, but can’t get the
exact FS value. It is not confirmed if the real FS value > or < 5.
In this regards, the NA option will be shown there. When NA shows, the assessment result save
will not be available showing below picture.