background image

Page 8

9) 

Check all the LED lights on the damper controllers again.    

 

 

If some of the lights are off, the cable to the first off-light  

 

 

 

damper controller could be crossed over. Check and replace it. 

10)

  Repeat step 9) until all of the lights are on and the LCD screen  

 

 

on the touchpad shows clock time and the room temperature  

 

 

where the touchpad is located after showing “initiate” on the   

 

second line for about 15 seconds. 

11) 

Hold down both            and            buttons on the touchpad for  

 

 

about 5 seconds to enter the setting mode (refer to next  

 

 

 

section). Check all the LED lights on the damper controllers   

 

again. All of the LED lights must be flashing in one-second    

 

 

interval. Otherwise, check the cable and the connection.

12) 

Turn off the power and disconnect the touchpad. 

13) 

Position the touchpad at the right place. Ideally, its position    

 

 

is approximate 1.6M off the floor on the wall. Fit the cable    

 

 

through the wall cavity and connect the touchpad again. 

14) 

Apply the power again to the transformer. The LCD should    

 

 

show clock time and temperature. If not, check the cable.

15) 

Mount the supply air sensor in the supply air duct upstream the  

 

 

motorised damper.

 

 

16) 

Fit the sensor cable through the   

 

 

 

wall cavity and plug into the socket  

 

 

 

 

on the back of the touchpad. 

 

 

17) 

Connect the battery by plugging into    

 

 

 

the socket on the back of the touchpad. 

 

 

 

 

 

 

battery

 

 

 

sensor

Summary of Contents for Zonemaster Unipoint

Page 1: ...UNIPOINT CONTROL SYSTEM Setup Guide Polyaire Pty Ltd 11 13 White Road GEPPS CROSS South Australia 5094 Tel 08 8349 8466 Fax 08 8349 8446 www polyaire com au...

Page 2: ......

Page 3: ...n the System 10 4 Supply Air Safety High Low Limits 11 5 Spill Bypass Air Setpoint 11 6 Naming Zones 13 7 Damper on off Test 13 Information Sheet 14 Trouble Shooting Guide 15 Specifications 16 Liabili...

Page 4: ...lised zone labelling Auto spill bypass the designated zones bypass are forced open when all zones are turned off Safety system Opens all dampers if the supply air temperature is less than low limit or...

Page 5: ...per drives the blade of the damper to turn on off the air from ducting to a zone 4 Bridge Cable Bridge cable connects the damper controller and the motorised damper together 5 Supply Air Sensor Supply...

Page 6: ...ct the touchpad dampers and power supply in series via a control bus as shown on Figure 1 Figure 2 shows another connection in which a double adaptor is used to connect the touchpad in the middle of t...

Page 7: ...Page 4 Figure 2 Wiring diagram 2...

Page 8: ...e damper controller 2 Allocate and set unique addresses to all zones with consideration of spill privileges for the zones Please refer to the Zone Address section for details Please note that bypass d...

Page 9: ...not plug the damper controller into any other motorised damper except a Polyaire authorised one 4 Apply the power to the transformer by plugging in the transformer into the 240VAC power outlet 5 Plug...

Page 10: ...be on If not check the cable and the connection 7 Repeat the step 6 until all damper controllers are connected together in series and all LED lights are on 8 Use another pre tested cable to connect t...

Page 11: ...damper controllers again All of the LED lights must be flashing in one second interval Otherwise check the cable and the connection 12 Turn off the power and disconnect the touchpad 13 Position the to...

Page 12: ...in Figure 3 When allocating address to each zone in spill mode it is strongly recommended to give lower addresses to those zones that have higher spill privileges The lower the address the higher the...

Page 13: ...ameter and provides more accurate temperature display 1 Using an accurate probe to measure the temperature of the area you want to calibrate and record the value 2 At the setting mode press button unt...

Page 14: ...from 45 C to 75 C 3 Press button once again the LCD screen will display the L_Limit 4 Press or button to change the low limit to the desired value The adjustable range of the low limit is from 0 C to...

Page 15: ...mber of open zones is less than its setpoint The bypass damper is also serially connected with other dampers and has a special address as mentioned before 1 At the setting mode press button until the...

Page 16: ...reset zone names for the zone 3 To make changes to the preset selected name press button to move to the character that is flashing 4 Use or button to select the character from the list as desired Ther...

Page 17: ...to assist installation and commissioning Address Default Name Custom Name Zone_1 Zone_2 Zone_3 Zone_4 Zone_5 Zone_6 Zone_7 Zone_8 Parameter Default Value Custom Value O F Zone Z1 Z8 High limit disable...

Page 18: ...he battery at first Reset the touchpad by turning off and turning on the power supply again If the display is normal plug in the battery again Dampers have no response when turning it on or off Check...

Page 19: ...tive humidity 10 to 80 Avoid static electricity hazards Avoid electromagnetic radiation sources Avoid dust contamination Avoid highly corrosive environments Touchpad Power input 24VAC 50Hz Dimensions...